{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-4EF32-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-4EF32-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-4EF32-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4EF32-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-4EF32-0AC0, 3-pole molded case circuit breaker, 160 A rated continuous current, TM240 thermal-magnetic release, 75.6 kA at 415 V, 70 mm depth, 76.2 mm width, 130 mm height.","salesMarkdown":"## MCCB for line protection — 160 A continuous, 3-pole, TM240 release Breaking capacity reaches 121 kA at 240 V and 75.6 kA at 415 V, which provides selectivity headroom for high-fault panelboards and main feeders. Above that it derates stepwise: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. For a panel enclosure running at 60 °C ambient, plan for 150.4 A continuous — not the full 160 A. The depth of 70 mm leaves room behind the panel door for wiring and auxiliary connections. ## Auxiliary contacts and lifecycle Two HQ auxiliary switches are integrated. No communication function, phase failure detection, or voltage trigger is present — this is a straight thermal-magnetic breaker for basic line protection.","metaTitle":"Siemens 3VA1116-4EF32-0AC0 SENTRON MCCB, 160 A, 3-Pole, 75.6","metaDescription":"Siemens SENTRON 3VA1116-4EF32-0AC0 molded case circuit breaker, 160 A rated continuous current, 3-pole, TM240 release, 75.6 kA at 415 V. Available to order; confirm current pricing","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 690 V":"11.9 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"800 A","Adjustable response value current / lr min.":"112 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=64367&mlfb=3VA1116-4EF32-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4EF32-0AC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1116-4EF32-0AC0 at 415 V?","answer":"At 415 V the breaking capacity is 75.6 kA."},{"question":"Where can I buy 3VA1116-4EF32-0AC0?","answer":"This part is sourced and quoted to order through independent distribution; submit an RFQ for current pricing and availability."},{"question":"Will 3VA1116-4EF32-0AC0 drop into a panel specified for 3VA1010-2ED32-0JA0?","answer":"Both are 3-pole SENTRON MCCBs with the same 130 mm height and 76.2 mm width, so the footprint matches. Verify the continuous current rating of the panel design — this unit is 160 A versus the lower-rated sibling — and confirm the TM release settings match the coordination study."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-4EF32-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-4EF32-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}