{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-4EF32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-4EF32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-4EF32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4EF32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-4EF32-0AH0, molded case circuit breaker (MCCB), 3-pole, 160 A at 40 °C, TM240 thermal-magnetic release, line protection, 70 mm depth.","salesMarkdown":"Rated 160 A continuously at 40 °C ambient, it derates slightly as the panel warms: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. Breaking capacity is stated per voltage: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. For a 480 V North American panel, the 52.5 kA at 440 V is the closest published figure — adequate for most industrial service-entrance or feeder duty where the available fault current is under 50 kA. Dimensions are 130 mm height, 76.2 mm width, and 70 mm depth — a compact 3-pole footprint that fits standard SENTRON mounting plates and busbar systems. Panel cut-out and busbar spacing match the 3VA family, so a drop-in replacement for an existing 3VA breaker of the same frame size requires no re-drilling or re-busing. That gives three discrete signals: one for breaker open/closed status, one for the spring-charged mechanism, and one dedicated to trip indication — enough for a PLC to distinguish a manual open from a fault trip without additional wiring. That heat must be considered in the enclosure thermal calculation — 38 W is not trivial in a sealed cabinet.","metaTitle":"Siemens 3VA1116-4EF32-0AH0 SENTRON MCCB, 160 A, 3-Pole, 70 m","metaDescription":"Siemens 3VA1116-4EF32-0AH0 SENTRON molded case circuit breaker, 160 A at 40 °C, 3-pole, 121 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11164EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=504811&mlfb=3VA1116-4EF32-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4EF32-0AH0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-4EF32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-4EF32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}