{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-4GD46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-4GD46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-4GD46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4GD46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-4GD46-0AA0, molded case circuit breaker, 160 A, 4-pole, TM210 thermal-magnetic release, line protection design, IP40 front.","salesMarkdown":"## 160 A fixed rating, 4-pole, TM210 — line protection for distribution panels Breaking capacity runs from 121 kA at 240 V down to 11.9 kA at 690 V, so the 415 V rating of 75.6 kA is the one to check against your available fault current. Above that it derates linearly: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C.","metaTitle":"Siemens 3VA1116-4GD46-0AA0 SENTRON MCCB, 160 A, 4-Pole, TM21","metaDescription":"Siemens SENTRON 3VA1116-4GD46-0AA0 molded case circuit breaker, 160 A fixed rating, 4-pole, TM210 release, 121 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"160 A","Minimum":"160 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9f615289c743128b8f3acace6990a349.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=141932&mlfb=3VA1116-4GD46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4GD46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-4GD46-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What is 3VA1116-4GD46-0AA0's listed depth (70 mm) on this component line?","answer":"The listed depth is 70 mm (2.76 in). Width is 101.6 mm (4 in), height is 130 mm (5.12 in). These dimensions match the standard 4-pole MCCB footprint for the SENTRON 3VA platform."},{"question":"Will 3VA1116-4GD46-0AA0 drop into a panel that was specified around 3VA1112-5EE32-0AA0 without rewiring?","answer":"Both are 4-pole SENTRON 3VA MCCBs on the same mechanical platform, so the mounting footprint and bus-bar centers are identical. The difference is the rating: 3VA1116-4GD46-0AA0 is a fixed 160 A with a TM210 release, while the 3VA1112-5EE32-0AA0 is a different amp rating and release type. If the panel was wired and braced for 160 A, the swap is mechanical — no rewiring needed. If the original was a lower rating, verify the bus and cable sizing can handle 160 A."},{"question":"What compliance documentation does this brand provide for 3VA1116-4GD46-0AA0 (RoHS, REACH, UL, IEC)?","answer":"As a Siemens SENTRON product, this MCCB carries the standard CE marking for the European market and is designed to IEC 60947-2. UL and CSA listings are typical for the 3VA platform, but the specific approvals for this order code should be confirmed from the manufacturer's declaration of conformity or the product certificate available through Siemens Industry Online Support."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-4GD46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-4GD46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}