{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-4GE42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-4GE42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-4GE42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4GE42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 series, IEC frame 160, breaking capacity class S, Icu=36kA @ 415V, 4-pole, line protection TM220, ATFM, In=160A, overload Ir=112A...160A, short-circuit Ii=10 x In, N conductor protection 100%, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1116-4GE42-0AA0-ZD00 is a 4-pole IEC molded case circuit breaker in the 3VA1 frame, sized for 160 A continuous current with a 36 kA interrupting capacity at 415 V (breaking capacity class S). The TM220 thermal-magnetic trip unit gives you adjustable overload protection from 112 A to 160 A and a fixed short-circuit pickup of 10 x In — meaning the magnetic trip fires at 1600 A. The 100% N-conductor protection means the neutral pole is fully rated, not derated, which matters for four-wire systems where the neutral carries phase imbalance or harmonics. The 160 A frame and 160 A continuous rating mean the breaker is fully rated (no derating needed at 40 °C ambient, typical for a 3VA1). The TM220 trip curve is a standard thermal-magnetic characteristic; the adjustable Ir band (112–160 A) lets you fine-tune overload protection to the downstream cable or load without swapping the trip unit.","metaTitle":"Siemens 3VA1116-4GE42-0AA0-ZD00 IEC Frame 160 MCCB, 160A, 36","metaDescription":"Siemens 3VA1116-4GE42-0AA0-ZD00 circuit breaker, IEC frame 160, 36kA @ 415V, 4-pole, 160A, TM220 overload. Lifecycle current. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/29f2d0d015f1f7c5394f9fcdcbff9c12.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667595&mlfb=3VA1116-4GE42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4GE42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-4GE42-0AA0-ZD00 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is the full specification of 3VA1116-4GE42-0AA0-ZD00?","answer":"It is a 3VA1 IEC frame 160 breaker, 4-pole, breaking capacity class S with Icu=36kA @ 415V, TM220 thermal-magnetic trip, In=160A, adjustable overload Ir=112A to 160A, fixed short-circuit Ii=10 x In, 100% N-conductor protection, and includes a nut keeper kit for DC Power OEM in China."},{"question":"What compliance documentation does this breaker carry?","answer":"The evidence does not list specific certifications (UL, CSA, CE, RoHS, REACH) for this order code. The 3VA1 series is typically IEC-rated; confirm the specific compliance package with the RFQ response."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-4GE42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-4GE42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}