{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5ED22-0AA0, molded case circuit breaker, 2-pole, 160 A, TM210 overcurrent release, line protection, 187 kA at 240 V AC, 121 kA at 415 V AC.","salesMarkdown":"The breaker is rated for a continuous current of 160 A across the 40 °C to 50 °C ambient range, then derates to 150 A at 70 °C. That derating curve matters if you are packing this into a warm enclosure — at 70 °C you lose 10 A of headroom. ## Breaking capacity — the real fault-handling number At 415 V, that is still a very high fault-current capability — enough for most industrial distribution panels downstream of a large transformer. If you are using it on a DC bus, check the 3VA device manual for DC-specific derating; the manufacturer flags that separately. The breaker measures 130 mm high, 50.8 mm wide (2 inches — standard MCCB pole spacing), and 70 mm deep. This is a straight thermal-magnetic breaker with a trip indicator absent; you will see the handle position, not a flag.","metaTitle":"Siemens 3VA1116-5ED22-0AA0 SENTRON MCCB, 2-Pole, 160A, 187kA","metaDescription":"Siemens 3VA1116-5ED22-0AA0 SENTRON molded case circuit breaker, 2-pole, 160A rated, TM210 release, 187kA breaking at 240V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.34 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2aca5f3b3d9d5eeca4fed8f7bf6a7963.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=694632&mlfb=3VA1116-5ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this MCCB?","answer":"It is a 2-pole, 160 A continuous rated breaker with a TM210 thermal-magnetic release. Breaking capacity is 187 kA at 240 V AC and 121 kA at 415 V AC. Rated insulation voltage is 500 V."},{"question":"Where can I buy the 3VA1116-5ED22-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the physical size of this breaker?","answer":"It measures 130 mm high, 50.8 mm wide (2 inches), and 70 mm deep."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}