{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5ED32-0AA0, molded case circuit breaker, 3-pole, TM210 thermal-magnetic release, 160 A at 40 °C, breaking capacity 187 kA at 240 V AC, IP40 front.","salesMarkdown":"Breaking capacity is the headline spec here: 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. That high interrupt rating at 240 V makes this breaker a strong candidate for high-fault service entrance or sub-distribution where available short-circuit current exceeds 100 kA — common in large industrial plants or utility tie points. Current derating is published across the full ambient range: 160 A up to 50 °C, then 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint that drops into SENTRON 3VA mounting bases and busbar adapters without modification. If those are needed for the application, they must be added externally via the 3VA accessory system — the breaker itself is a straight thermal-magnetic line-protection device.","metaTitle":"Siemens 3VA1116-5ED32-0AA0 SENTRON MCCB, 160 A, 3-Pole, TM21","metaDescription":"Siemens 3VA1116-5ED32-0AA0 SENTRON molded case circuit breaker, 160 A rated at 40 °C, 3-pole, TM210 release, 187 kA at 240 V. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8f8831798c90a7eba265bec20986abb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=357379&mlfb=3VA1116-5ED32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1116-5ED32-0AA0 at 240 V?","answer":"187 kA at 240 V AC, with 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V."},{"question":"What is the continuous current rating of 3VA1116-5ED32-0AA0 at elevated temperatures?","answer":"160 A up to 50 °C, then derated to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C."},{"question":"Where can I buy 3VA1116-5ED32-0AA0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}