{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 circuit breaker, 3-pole, breaking capacity class M, Icu=55kA @ 415 V, line protection TM210, FTFM, In=160 A, Ir=160 A fixed, Ii=10 x In, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1116-5ED32-0AA0-ZD00 is a 3VA1 IEC frame 160 molded-case circuit breaker, 3-pole, with a 55 kA Icu at 415 V — that is the breaking capacity class M rating, meaning it can safely interrupt a fault current up to 55,000 A at that voltage without external fuses or cascading upstream. It is configured for line protection with a TM210 thermal-magnetic trip unit: fixed overload protection at Ir = 160 A and fixed short-circuit protection at Ii = 10 x In, so the magnetic pickup fires at 1,600 A.","metaTitle":"3VA1116-5ED32-0AA0-ZD00 Circuit Breaker 3VA1, 160A, 55kA @ 4","metaDescription":"Siemens 3VA1116-5ED32-0AA0-ZD00 circuit breaker, 3VA1 IEC frame 160, 3-pole, 55kA Icu @ 415V, TM210 line protection, 160A fixed Ir, 10x In Ii. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f606d3d1c7fa681bf73f144750dcbc2f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667597&mlfb=3VA1116-5ED32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1116-5ED32-0AA0-ZD00?","answer":"The breaking capacity class M gives an Icu of 55 kA at 415 V AC, 3-pole."},{"question":"What trip unit does this breaker use?","answer":"It uses a TM210 thermal-magnetic trip unit with fixed overload protection Ir = 160 A and fixed short-circuit protection Ii = 10 x In (1,600 A)."},{"question":"Where can I buy 3VA1116-5ED32-0AA0-ZD00?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}