{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA molded case circuit breaker, 3VA1116-5ED32-0AB0, 160 A, 3-pole, line protection, TM210 thermal-magnetic release, 187 kA interrupting at 240 V.","salesMarkdown":"## 160 A, 187 kA interrupting — the numbers that matter for your panel The Siemens 3VA1116-5ED32-0AB0 is a SENTRON molded case circuit breaker (MCCB) rated for 160 A continuous current at 40 °C, across a 3-pole configuration. Its interrupting capacity hits 187 kA at 240 V and 121 kA at 415 V — figures that govern whether this breaker clears a fault without upstream damage in high-available-fault-current panels. No undervoltage release, no phase-failure detection, no communication function — this is a straight line-protection breaker, not a multifunction device. The 160 A rating holds flat from 40 °C to 50 °C, then derates to 153.6 A at 55 °C and 144 A at 70 °C. If your panel ambient runs hot, that 144 A at 70 °C is the real limit — not the nameplate 160 A. The 187 kA at 240 V is the peak short-circuit current this breaker can safely interrupt; at 690 V it drops to 17 kA, so verify the available fault current at your service voltage. ## Panel fit and auxiliary contacts The breaker measures 70 mm deep, 76.2 mm wide, and 130 mm tall. No voltage trigger or undervoltage release is fitted; if you need undervoltage protection, this variant won't do it without an add-on accessory.","metaTitle":"Siemens 3VA1116-5ED32-0AB0 SENTRON MCCB, 160 A, 3-Pole, 187","metaDescription":"Siemens 3VA1116-5ED32-0AB0 SENTRON molded case circuit breaker. 160 A continuous, 3-pole, 187 kA at 240 V. TM210 release. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"160 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=303133&mlfb=3VA1116-5ED32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0AB0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1116-5ED32-0AB0?","answer":"Current pricing and availability are confirmed at quote time against an RFQ through independent distribution. Submit a request for a firm quote with your quantity and delivery timeline."},{"question":"What are the key ratings of 3VA1116-5ED32-0AB0?","answer":"This 3-pole SENTRON MCCB is rated for 160 A continuous current (flat to 50 °C, derating to 144 A at 70 °C), with interrupting capacity of 187 kA at 240 V, 121 kA at 415 V, and 17 kA at 690 V. It uses a TM210 thermal-magnetic release and carries an 800 V rated insulation voltage."},{"question":"Will 3VA1116-5ED32-0AB0 drop into a panel that was specified around 3VA1112-5EF32-0CA0 without rewiring?","answer":"Both breakers share the same SENTRON 3VA platform dimensions (70 mm deep, 76.2 mm wide, 130 mm tall) and 3-pole form factor, so the mechanical fit and bus-bar spacing are identical. The difference is the current rating — the 3VA1116-5ED32-0AB0 is a 160 A frame versus the 3VA1112-5EF32-0CA0's lower rating — so verify the load and conductor sizing before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}