{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED32-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED32-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5ED32-0AF0, molded case circuit breaker, 3-pole, 160 A, TM210 overcurrent release, 187 kA breaking capacity at 240 V, IP40 front.","salesMarkdown":"The Siemens SENTRON 3VA1116-5ED32-0AF0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 160 A. That 160 A holds flat from 40 °C through 50 °C ambient, then derates to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C — so in a warm enclosure the breaker still carries 144 A before the TM210 thermal-magnetic release starts its curve. The TM210 designation means the thermal element is fixed at 160 A (the Iu) and the magnetic short-circuit pickup is 10× Iu, or 1600 A, which is the standard setting for general distribution and motor-circuit protection where you need to ride through inrush without nuisance tripping. Breaking capacity is the headline: 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. For a 415 V distribution panel with a transformer feeding a high-fault-current bus, 121 kA gives you headroom over a typical 50–65 kA available fault current, so you can use this breaker downstream without worrying about cascading failure. The 187 kA at 240 V is relevant for single-phase or line-to-neutral faults in 240/415 V systems. Rated insulation voltage Ui is 800 V, and maximum DC operational voltage Ue is 500 V — so the breaker is rated for DC circuits up to 500 V, though the DC breaking capacity curve is not listed here and should be checked against the device manual for the specific DC configuration. Dimensions are 76.2 mm wide, 130 mm high, and 70 mm deep. That 76.2 mm width is a standard 3-pole MCCB footprint on a DIN rail or mounting plate — it occupies three 25.4 mm module spaces.","metaTitle":"Siemens 3VA1116-5ED32-0AF0 SENTRON MCCB, 160 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA1116-5ED32-0AF0 molded case circuit breaker, 160 A rated, 3-pole, TM210 release, 187 kA breaking at 240 V. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip Indicator":"Yes","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11165ED320AA0","Courant permanent assigné Iu":"160 A","Design Of The Auxiliary Release":"without auxiliaryrelease","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg min.":"1","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"lug terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=114673&mlfb=3VA1116-5ED32-0AF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0AF0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1116-5ED32-0AF0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is 3VA1116-5ED32-0AF0's listed depth?","answer":"The depth is 70 mm, with a width of 76.2 mm and height of 130 mm."},{"question":"What is the breaking capacity of 3VA1116-5ED32-0AF0 at 415 V?","answer":"121 kA at 415 V AC, with 187 kA at 240 V, 75.6 kA at 440 V, and 17 kA at 690 V."},{"question":"What overcurrent release does this breaker use?","answer":"The TM210 release — a thermal-magnetic trip with fixed thermal at 160 A and magnetic pickup at 10× Iu (1600 A)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED32-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}