{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5ED32-0CC0, molded case circuit breaker, 3-pole, 160 A at 40 °C, 187 kA breaking capacity at 240 V, line protection design.","salesMarkdown":"Its continuous current rating holds at 160 A from 40 °C up through 50 °C, then derates to 150 A at 70 °C, so you can size it for a 160 A feeder in a warm enclosure without oversizing. ## Built-in auxiliaries and release — what you get on the frame The auxiliary switches give status feedback (open/closed/tripped) to a PLC or indicator lamp. No communication module is included, so this is a standalone breaker for hardwired panels. The frame dimensions are 130 mm height, 76.2 mm width, 70 mm depth — fits standard SENTRON 3VA mounting footprints and accepts the same busbar and terminal accessories as the rest of the 3VA1 family. ## How it compares to the 3VA1110-5ED36-0AC0 The closest sibling in the SENTRON 3VA family is the 3VA1110-5ED36-0AC0. The key difference: the 3VA1116-5ED32-0CC0 is rated 160 A continuous, while the 3VA1110-5ED36-0AC0 is rated 100 A. If your BOM calls for a 160 A feeder, the 3VA1110 will not carry the load — you need this 160 A frame. The physical mounting and busbar kits are shared, so a panel drilled for the 100 A version accepts the 160 A unit without rework.","metaTitle":"Siemens 3VA1116-5ED32-0CC0 SENTRON MCCB, 160 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA1116-5ED32-0CC0 molded case circuit breaker, 160 A, 3-pole, 187 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11165ED320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=298969&mlfb=3VA1116-5ED32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-5ED32-0CC0 and how is it quoted?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or price is published here."},{"question":"What is the breaking capacity of 3VA1116-5ED32-0CC0 at 240 V?","answer":"At 240 V the interrupting rating is 187 kA. At 415 V it is 121 kA, at 440 V it is 75.6 kA, and at 500 V and 690 V it is 17 kA."},{"question":"Will 3VA1116-5ED32-0CC0 drop into a panel specified for 3VA1110-5ED36-0AC0?","answer":"Yes — both share the same 70 mm depth and 76.2 mm width, and the mounting footprint and busbar kits are identical. The 160 A frame fits without rewiring or drilling changes."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}