{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED32-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED32-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5ED32-0DC0, Molded case circuit breaker, 3-pole, 160 A, TM210 thermal-magnetic release, 187 kA interrupting at 240 V, IP40 front.","salesMarkdown":"## SENTRON 3VA1116-5ED32-0DC0 — 160 A MCCB with TM210 Release It delivers 187 kA interrupting capacity at 240 V, 121 kA at 415 V, and 75.6 kA at 440 V — numbers that govern the available fault current the breaker can safely clear without upstream coordination failure. The TM210 release provides thermal protection for overloads and magnetic instantaneous trip for short circuits — a standard choice for feeder and branch circuit protection in commercial and industrial switchboards. ## Interrupting Capacity and Thermal Derating At 690 V the interrupting rating drops to 17 kA — verify system fault levels if deploying on 600 V class equipment. The 160 A rating holds flat from 40 °C through 50 °C, then derates to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. ## Panel Fit and Lifecycle Footprint is 76.2 mm wide × 130 mm tall × 70 mm deep — standard 3-pole MCCB envelope for DIN-rail or panel-mount installation.","metaTitle":"Siemens 3VA1116-5ED32-0DC0 SENTRON MCCB, 160 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA1116-5ED32-0DC0 molded case circuit breaker, 160 A rated, 3-pole, TM210 release, 187 kA at 240 V. Currently in production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"160 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=308701&mlfb=3VA1116-5ED32-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0DC0/alternatives.json"},"ai":{"faq":[{"question":"What are the interrupting ratings for 3VA1116-5ED32-0DC0?","answer":"187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. These values govern the maximum fault current the breaker can safely clear at each voltage level."},{"question":"How does temperature affect the 160 A rating on this MCCB?","answer":"The 160 A rating holds from 40 °C to 50 °C, then derates to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. Panel ambient temperature inside the enclosure determines actual continuous current capacity."},{"question":"Where can I buy 3VA1116-5ED32-0DC0 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"Does 3VA1116-5ED32-0DC0 include auxiliary contacts or an undervoltage release?","answer":"Yes, it ships with 2 HQ auxiliary switches and an integrated undervoltage release (UVR) as standard equipment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED32-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}