{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5ED32-0JH0, Molded case circuit breaker, 3-pole, 160 A, TM210 overcurrent release, line protection, shunt trip STL, IP40 front.","salesMarkdown":"The TM210 designation means the thermal pickup is fixed at 160 A — no field-adjustable dial — and the magnetic short-circuit trip is set at 10× In (1600 A). This is a line-protection version, not a motor-protection or ground-fault variant, so it is sized for feeder or main breaker duty in distribution panels, not for individual motor starting circuits. The interrupting ratings are the headline: 187 kA at 240 V AC, 121 kA at 415 V AC, 75.6 kA at 440 V AC, and 17 kA at 690 V AC. That is a high-interrupting-capacity (HIC) class device, not a standard 25–50 kA MCCB. Thermal derating is flat from 40 °C to 50 °C at 160 A, then drops to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. If the panel ambient runs at 60 °C, you lose about 6% of the rated current — plan the load accordingly. ## Panel fit and auxiliary configuration The 76.2 mm width is a standard 3-pole MCCB footprint for this current class — it occupies three 25.4 mm pole spaces on a DIN rail or panel-mount base. The shunt trip (STL) release is built in — order code 3VA9688-0BL32 for the integrated auxiliary trip module. No undervoltage release, no communication function, no phase failure detection, no ground fault monitoring. This is a bare-bones line protection breaker with remote trip capability and status feedback, but no metering or network integration. Front protection is IP40 — suitable for dry indoor panel environments. The latching endurance is rated at 15,000 operations, which is typical for a distribution MCCB not cycled daily.","metaTitle":"Siemens 3VA1116-5ED32-0JH0 SENTRON MCCB, 160 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA1116-5ED32-0JH0 molded case circuit breaker, 160 A rated continuous current, 3-pole, line protection, TM210 release, 187 kA at 240 V. Active production. Quoted t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"160 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=406870&mlfb=3VA1116-5ED32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA1116-5ED32-0JH0 at 415 V?","answer":"At 415 V AC, the interrupting rating is 121 kA. At 240 V it is 187 kA, at 440 V it is 75.6 kA, and at 690 V it is 17 kA."},{"question":"What is the width of 3VA1116-5ED32-0JH0?","answer":"The width is 76.2 mm, which is standard for a 3-pole MCCB in this current class — three 25.4 mm pole spaces."},{"question":"What is the depth of 3VA1116-5ED32-0JH0?","answer":"The depth is 70 mm, shallow enough for most 200 mm deep enclosures with wiring gutters."},{"question":"Where can I buy 3VA1116-5ED32-0JH0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here."},{"question":"What compliance documentation does this breaker carry?","answer":"The SENTRON 3VA series is designed to meet IEC 60947-2 and UL 489 standards for molded case circuit breakers. RoHS and REACH compliance documentation is available from Siemens. Specific certification marks (UL, CSA, CE) should be verified against the nameplate for the exact variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}