{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED36-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED36-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED36-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED36-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5ED36-0AC0, 3-pole molded case circuit breaker, 160 A rated current Iu, TM210 thermal-magnetic release, line protection version, IP40 front, 187 kA interrupting at 240 V.","salesMarkdown":"The thermal derating curve is flat up to 50 °C — still 160 A — then drops to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. The auxiliary contact version ships with 2 HQ switches, giving status feedback for the open/closed position. The 3VA1116-5ED36-0AC0 measures 130 mm high, 3 in wide, and 2.8 in deep. The 3-pole footprint matches the SENTRON 3VA family, so busbar and cable connections follow the same pattern as other 160 A frames in the range.","metaTitle":"Siemens 3VA1116-5ED36-0AC0 SENTRON MCCB, 160 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA1116-5ED36-0AC0 molded case circuit breaker, 160 A, 3-pole, TM210 release, 187 kA at 240 V. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"76 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.8 in","Width [In]":"3 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11165ED360AA0","Courant permanent assigné Iu":"160 A","Design Of The Auxiliary Release":"without auxiliaryrelease","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg min.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1338191&mlfb=3VA1116-5ED36-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED36-0AC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-5ED36-0AC0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution channels. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What are the interrupting ratings for 3VA1116-5ED36-0AC0 at different voltages?","answer":"The breaker is rated 187 kA at 240 V, 121 kA at 415 V, 76 kA at 440 V, and 17 kA at both 500 V and 690 V AC."},{"question":"What is the height of 3VA1116-5ED36-0AC0?","answer":"The listed height is 130 mm."},{"question":"Does 3VA1116-5ED36-0AC0 include an undervoltage release or ground-fault monitoring?","answer":"No — this variant ships without an undervoltage release, without ground-fault monitoring, and without a voltage trigger. It is a straight line-protection breaker with a TM210 thermal-magnetic release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED36-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED36-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}