{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5ED42-0AA0, molded case circuit breaker, 4-pole, 160 A, TM210 release, line protection, 187 kA at 240 V AC.","salesMarkdown":"## Part identity and key ratings It carries a continuous current rating of 160 A across the 40 °C to 50 °C ambient band, derating to 150 A at 70 °C. The interrupting capacity is 187 kA at 240 V AC, 121 kA at 415 V AC, 75.6 kA at 440 V AC, and 17 kA at both 500 V and 690 V AC. The TM210 release means the thermal element handles overloads and the magnetic element handles short circuits — no electronic trip unit adjustments, so it's a fixed-characteristic breaker for straightforward line protection. The 4-pole configuration covers three-phase plus neutral, or can be used as a four-wire disconnect. The 101.6 mm (4-inch) width is standard for a 4-pole MCCB in this frame size — check your enclosure's back-panel or DIN-rail layout for that footprint. Front IP40 protection means it's splash-proof from the front but not sealed against dust ingress around the sides or rear; mount it inside a panel with a door, not in an open washdown zone.","metaTitle":"Siemens 3VA1116-5ED42-0AA0 SENTRON MCCB, 4P, 160A, 187kA at","metaDescription":"Siemens SENTRON 3VA1116-5ED42-0AA0 molded case circuit breaker, 4-pole, 160 A rated at 40-50°C, 187 kA interrupting at 240 V AC. Line protection, TM210 release. Current lifecycle s","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"without","operating voltage / at AC / rated value":"690 V","Max. rated operational voltage Ue with DC":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6,5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ae0aac3fb36de2cd91102a5e205e78c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=382212&mlfb=3VA1116-5ED42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1116-5ED42-0AA0 at 415 V?","answer":"At 415 V AC, the interrupting capacity is 121 kA."},{"question":"How do I get pricing and availability for 3VA1116-5ED42-0AA0?","answer":"Submit an RFQ through this listing; availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional alternative to 3VA1116-5ED42-0AA0?","answer":"The 3VA1112-5EE36-0AA0 is a peer in the same SENTRON 3VA family but with a different current rating and release — verify your load requirements before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}