{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5ED46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5ED46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5ED46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5ED46-0AA0, molded case circuit breaker, 4-pole, 160 A, TM210 release, 187 kA at 240 V, IP40 front.","salesMarkdown":"## What the 160 A rating means for your panel The TM210 thermal-magnetic release handles overloads and short-circuits in one package. At 45 °C it still holds 160 A; at 55 °C it derates to 158 A, and at 70 °C it's 150 A, so if your panel runs hot, you lose 10 A off the top. Breaking capacity is the real fit question. This 4-pole unit clears 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500 V and 690 V. That covers most low-voltage distribution panels in North America (240/480 V) and Europe (400/415 V). The 690 V rating at 17 kA is useful for 600 V class Canadian panels or some industrial drives. Footprint is 70 mm deep, 101.6 mm wide, 130 mm tall — standard SENTRON 3VA form factor. Four-pole width at 101.6 mm means it occupies two 50 mm DIN-rail slots or a single wide cutout in a panel gland plate. IP40 on the front keeps fingers out but is not washdown-rated. ## Integration notes Insulation voltage rated 800 V. For motor branch circuits, pair it with a separate overload relay.","metaTitle":"Siemens 3VA1116-5ED46-0AA0 SENTRON MCCB, 160A, 4-Pole, TM210","metaDescription":"Siemens 3VA1116-5ED46-0AA0 SENTRON molded case circuit breaker, 160A rated at 40°C, 4-pole, TM210 release, 187 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"without","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bd7933d6ae6874fba53b15905f786e26.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=314057&mlfb=3VA1116-5ED46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5ED46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3VA1116-5ED46-0AA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will the 3VA1116-5ED46-0AA0 drop into a panel specified for 3VA1112-5EE32-0AA0?","answer":"The 3VA1116-5ED46-0AA0 shares the same SENTRON 3VA form factor (70 mm deep, 101.6 mm wide, 130 mm tall) and DIN-rail mounting, so physical fit is the same. The difference is rating: this is 160 A / 4-pole / TM210, while the 3VA1112-5EE32-0AA0 is a lower-current variant. Verify the trip curve and interrupting capacity match your panel's fault study before swapping."},{"question":"What compliance documentation does the 3VA1116-5ED46-0AA0 carry?","answer":"As a Siemens SENTRON MCCB, it is designed to meet IEC 60947-2 and UL 489 standards. RoHS and REACH declarations are standard for the series. Specific certification marks (UL, CSA, CE) should be verified on the nameplate or via the Siemens documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5ED46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5ED46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}