{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5EE32-0DH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5EE32-0DH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5EE32-0DH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5EE32-0DH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5EE32-0DH0, molded case circuit breaker, 160 A, 3-pole, TM220 thermal-magnetic release, line protection, 187 kA at 240 V, 121 kA at 415 V.","salesMarkdown":"## What this MCCB does on the line The Siemens 3VA1116-5EE32-0DH0 is a SENTRON molded case circuit breaker (MCCB) sized for 160 A continuous duty — that's the rated current Iu, and it holds that rating from 40 °C all the way up to 50 °C before it starts to derate (153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C). The interrupting ratings are what you'd spec around: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. That's serious fault-current headroom for a 160 A frame — it'll clear a hard short without the arc climbing upstream. ## Footprint and fit The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard 3-pole MCCB footprint for this current class. It's a panel-mount unit with screw terminals; no DIN-rail clip on this frame size.","metaTitle":"Siemens 3VA1116-5EE32-0DH0 SENTRON MCCB, 160 A, 3-Pole, Line","metaDescription":"Siemens 3VA1116-5EE32-0DH0 SENTRON molded case circuit breaker, 160 A rated, 3-pole, TM220 release, 187 kA at 240 V. Current lifecycle stage, available to order. Request quote for","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM220","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"112 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=320357&mlfb=3VA1116-5EE32-0DH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5EE32-0DH0/alternatives.json"},"ai":{"faq":[{"question":"Does the 3VA1116-5EE32-0DH0 include auxiliary contacts?","answer":"Yes, it comes with 2 auxiliary switches and 1 trip alarm switch (HQ type) factory-installed. It also includes an undervoltage release (UVR) as the auxiliary release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5EE32-0DH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5EE32-0DH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}