{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5EE32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5EE32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5EE32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5EE32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5EE32-0JA0, molded case circuit breaker, 3-pole, 160 A, TM220 overcurrent release, shunt trip, IP40 front.","salesMarkdown":"Its interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — the 187 kA figure at 240 V means it can safely clear a fault up to that level without upstream devices needing to trip, which is critical for high-fault panels near large transformers or utility feeds. The overcurrent release is a TM220 thermal-magnetic design, so it provides both overload (thermal) and short-circuit (magnetic) protection in one unit. Above that, it derates: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. That derating curve matters for panel builders stuffing breakers into a warm enclosure — if your cabinet ambient sits at 60 °C, plan for 150.4 A continuous, not 160 A. ## Shunt trip and auxiliary trip options The integrated auxiliary trip uses order code 3VA9688-0BL32. The trip indicator is also absent, so you won't get a local mechanical flag showing a trip event; you'd need the panel indication or a separate auxiliary contact for that.","metaTitle":"Siemens 3VA1116-5EE32-0JA0 SENTRON MCCB, 160 A, 187 kA at 24","metaDescription":"Siemens 3VA1116-5EE32-0JA0 SENTRON molded case circuit breaker, 160 A rated, 3-pole, TM220 release, 187 kA at 240 V. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM220","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"112 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1720fcc47afb695b372e379589a63b55.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=55261&mlfb=3VA1116-5EE32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5EE32-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-5EE32-0JA0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm availability and current pricing."},{"question":"What is the closest functional second-source to 3VA1116-5EE32-0JA0?","answer":"Within the SENTRON 3VA family, a 3VA1010 variant is the closest functional peer, but it carries a lower current rating and different overcurrent release. Verify the interrupting capacity and frame size against your fault study before substituting."},{"question":"What is the depth of 3VA1116-5EE32-0JA0?","answer":"The depth is 70 mm."},{"question":"What is the width of 3VA1116-5EE32-0JA0?","answer":"The width is 76.2 mm."},{"question":"Will 3VA1116-5EE32-0JA0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?","answer":"Not without checking. The 3VA1010 variant has a different frame size and current rating — verify the mounting footprint, bus bar spacing, and cable lug dimensions against your existing panel layout before assuming a drop-in fit."},{"question":"What compliance documentation does Siemens provide for 3VA1116-5EE32-0JA0?","answer":"As a SENTRON MCCB, this part is designed to meet applicable IEC and UL standards for molded case circuit breakers. Specific RoHS, REACH, UL, and IEC declarations are available from Siemens upon request or through their product documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5EE32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5EE32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}