{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5EE42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5EE42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5EE42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5EE42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5EE42-0AA0, molded case circuit breaker, 4-pole, 160 A (40 °C), TM220 thermal-magnetic release, 187 kA at 240 V AC.","salesMarkdown":"## SENTRON 3VA1116-5EE42-0AA0 — 160 A MCCB for Line Protection Breaking capacity is 187 kA at 240 V AC, 121 kA at 415 V, and 75.6 kA at 440 V, with a floor of 17 kA at 500 V and 690 V. The breaker measures 130 mm high, 101.6 mm wide, and 70 mm deep — a standard 4-pole MCCB footprint for panel-mount installation. Front-face protection is IP40, suitable for enclosed distribution boards where splash and tool ingress are controlled.","metaTitle":"Siemens 3VA1116-5EE42-0AA0 SENTRON MCCB, 160 A, 4-Pole, TM22","metaDescription":"Siemens 3VA1116-5EE42-0AA0 SENTRON molded case circuit breaker, 160 A rated at 40 °C, 4-pole, TM220 release, 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"without","operating voltage / at AC / rated value":"690 V","Max. rated operational voltage Ue with DC":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Switching Cycles) / Typical":"20 000","reference value setting current (Ii) / for I-tripping":"x In","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","type of value list setting current (Ii) / for I-tripping":"Fest","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6,5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=271563&mlfb=3VA1116-5EE42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5EE42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What does the TM220 trip unit designation mean?","answer":"TM220 indicates a thermal-magnetic fixed-trip release — the thermal element handles overload protection, and the magnetic element handles short-circuit protection. It is a non-adjustable, line-protection configuration."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5EE42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5EE42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}