{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5EE42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5EE42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5EE42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5EE42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 4-pole, line protection TM220, ATFM, In=160A, overload protection Ir=112A...160A, short-circuit protection Ii=10 x In, N conductor unprotected, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1116-5EE42-0AA0-ZD00 is a 4-pole IEC frame 160 circuit breaker rated for line protection, carrying a 160 A continuous current rating (In) and a 55 kA ultimate breaking capacity (Icu) at 415 V AC — class M breaking capacity. The TM220 thermal-magnetic trip unit gives adjustable overload protection (Ir) from 112 A to 160 A, matching the conductor or load ampacity, and a fixed short-circuit pickup (Ii) at 10× In, so it clears bolted faults fast while riding through motor inrush. The 4-pole footprint occupies four module widths on the rail; the nut keeper kit (included per the order-code suffix) is a detail for the DC Power OEM variant destined for China — it holds the terminal nuts captive during assembly, saving a hand on the line.","metaTitle":"Siemens 3VA1116-5EE42-0AA0-ZD00 Circuit Breaker, 160A, 55kA","metaDescription":"Siemens 3VA1116-5EE42-0AA0-ZD00 IEC frame 160 circuit breaker, 55kA breaking capacity at 415V, 160A rated current. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fbe45b93f144e1a52871b3bc39b9fec7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667600&mlfb=3VA1116-5EE42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5EE42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this Siemens 3VA1 breaker?","answer":"The ultimate breaking capacity (Icu) is 55 kA at 415 V AC, class M, which is the standard high-fault rating for IEC distribution panels in industrial and commercial installations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5EE42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5EE42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}