{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-5EF32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-5EF32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-5EF32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5EF32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-5EF32-0JH0, molded case circuit breaker, 3-pole, 160 A continuous rating, 187 kA breaking capacity at 240 V, line protection design with integrated shunt trip release.","salesMarkdown":"## Rating and Application Context The Siemens 3VA1116-5EF32-0JH0 is a 3-pole SENTRON molded case circuit breaker rated for 160 A continuous current across the 40 °C to 50 °C ambient range, derating to 150 A at 70 °C. The breaker occupies a 76.2 mm width, 130 mm height, and 70 mm depth footprint. Panel cutout and mounting hole pattern follow the standard SENTRON 3VA frame dimensions; verify back-panel clearance for the shunt trip wiring and auxiliary switch terminations before committing the assembly. ## Breaking Capacity by Voltage Level Breaking capacity varies with system voltage: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. ## Environmental and Auxiliary Specifications Maximum power loss is 38 W. The breaker includes a trip indicator and voltage trigger function. No undervoltage release, ground-fault monitoring, or communication function is fitted on this variant.","metaTitle":"Siemens 3VA1116-5EF32-0JH0 SENTRON MCCB, 160 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA1116-5EF32-0JH0 molded case circuit breaker, 160 A continuous, 3-pole, 187 kA breaking at 240 V. Line protection with shunt trip. Current lifecycle stage. Source","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11165EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=100312&mlfb=3VA1116-5EF32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-5EF32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-5EF32-0JH0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the depth of 3VA1116-5EF32-0JH0?","answer":"The listed depth is 70 mm (2.76 in)."},{"question":"What is the width of 3VA1116-5EF32-0JH0?","answer":"The listed width is 76.2 mm (3 in)."},{"question":"Will 3VA1116-5EF32-0JH0 drop into a panel specified for 3VA1110-5EF32-0AM0 without rewiring?","answer":"Both breakers share the same SENTRON 3VA frame dimensions (76.2 mm width, 130 mm height, 70 mm depth), so the mechanical fit is identical. However, the 3VA1116-5EF32-0JH0 carries a 160 A continuous rating versus the 3VA1110-5EF32-0AM0's lower rating; verify that the busbar and cable sizing, as well as the protective device coordination study, support the higher ampacity before direct substitution."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"As a SENTRON series molded case circuit breaker, this part is designed to meet IEC 60947-2 and UL 489 standards. The manufacturer typically provides a Declaration of Conformity covering the Low Voltage Directive, RoHS, and REACH compliance upon request. Specific certificate numbers should be verified against the nameplate marking on the delivered unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-5EF32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-5EF32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}