{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA1116-6ED32-0AA0, molded case circuit breaker, 3-pole, TM210 thermal-magnetic release, 160 A at 40 °C, breaking capacity 220 kA at 240 V, 154 kA at 415 V, IP40 front, 70 mm depth.","salesMarkdown":"## What the 160 A rating and breaking capacity mean for your panel That 160 A holds steady across 40–50 °C ambient, then derates to 150 A at 70 °C; if your panel runs hot near the top of a sealed enclosure, you lose 10 A off the top end. The breaking capacity is what sets this MCCB apart for high-fault installations: 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500/690 V. ## Panel fit and mounting — 3-pole, 70 mm deep, IP40 front Three-pole construction, 76.2 mm wide, 130 mm tall, and 70 mm deep — that depth is the dimension from the mounting surface to the front, so it clears a standard 80 mm deep enclosure without door interference. ## Power loss and thermal management — 38 W at rated load Maximum power loss is 38 W at rated current — that heat has to go somewhere inside the enclosure. In a multi-breaker panel, sum the losses and check the enclosure's dissipation curve; 38 W per MCCB adds up fast in a 12-way distribution board. ## No communication, no trip indicator, no undervoltage release — pure line protection This variant is stripped for basic line protection: no communication function, no undervoltage release, no trip indicator, no ground-fault monitoring. The TM210 release is a thermal-magnetic type — no electronic adjustment, no zone-selective interlocking. If you need remote signaling or adjustable trip curves, look at the 3VA electronic-trip variants; this one is for fixed-threshold, hardwired distribution where simplicity and high interrupting capacity are the priority.","metaTitle":"SENTRON 3VA1116-6ED32-0AA0 MCCB, 160A, 3-Pole, TM210, 220kA@","metaDescription":"SENTRON 3VA1116-6ED32-0AA0 molded case circuit breaker, 160A rated at 40°C, 3-pole, TM210 release, 220kA breaking capacity at 240V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=193466&mlfb=3VA1116-6ED32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6ED32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1116-6ED32-0AA0?","answer":"Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the storefront or contact the sourcing desk; the part is sourced via independent distribution channels."},{"question":"Will 3VA1116-6ED32-0AA0 drop into a panel specified around 5SQ2370-2YA05 without rewiring?","answer":"The 3VA1116-6ED32-0AA0 is a 3-pole MCCB with 76.2 mm width and 70 mm depth, but the 5SQ2370-2YA05 is a different form factor and terminal arrangement. Do not assume a direct mechanical swap without checking the mounting footprint and bus bar centers. The electrical ratings (160 A, TM210) may be functionally close, but physical fit must be verified against the existing panel layout."},{"question":"What compliance documentation does this brand provide for 3VA1116-6ED32-0AA0?","answer":"SENTRON MCCBs carry IEC/EN 60947-2 certification. Compliance documentation including RoHS and REACH declarations is available from the manufacturer's support portal or through the distributor upon request. The IP40 front rating and 800 V rated insulation voltage are per IEC standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}