{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6ED32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6ED32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6ED32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6ED32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class H, Icu=70kA @ 415V, 3-pole, line protection TM210, FTFM, In=160A, Ir=160A fixed, Ii=10 x In, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1116-6ED32-0AA0-ZD00 is a 3-pole IEC frame 160 molded case circuit breaker rated for 160 A continuous current, with a fixed thermal-magnetic TM210 trip unit. The fixed overload protection (Ir = 160 A) and fixed short-circuit pickup (Ii = 10 × In = 1600 A) simplify BOM consistency: every unit in the line delivers identical trip coordination, no field-adjustment risk. ## Deployment context The 70 kA SCCR at 415 V makes it suitable for main or branch protection in industrial switchboards where transformer or generator-fed fault levels are high — a right-sized spec for most plant distribution without over-specifying to the next frame class.","metaTitle":"Siemens 3VA1116-6ED32-0AA0-ZD00 Circuit Breaker, 70kA @ 415V","metaDescription":"Siemens 3VA1116-6ED32-0AA0-ZD00 IEC frame 160 circuit breaker, 70kA breaking capacity at 415V, 160A fixed overload, 10x In short-circuit protection. Current lifecycle stage. Quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f28742dd6b851302d270ff4c8723c48c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667606&mlfb=3VA1116-6ED32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6ED32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-6ED32-0AA0-ZD00 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or price is published here, but a quote request will return a firm offer."},{"question":"What are the key ratings of 3VA1116-6ED32-0AA0-ZD00?","answer":"The breaker is rated 160 A continuous (In), with fixed overload protection at Ir = 160 A and fixed short-circuit pickup at Ii = 10 × In (1600 A). Its breaking capacity is 70 kA at 415 V AC (class H), and it is a 3-pole IEC frame 160 device with a TM210 thermal-magnetic trip unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6ED32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6ED32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}