{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6ED36-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6ED36-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6ED36-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6ED36-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 series, IEC frame 160, breaking capacity class H, 3-pole, line protection TM210, In=160A, Icu=70kA @ 415V, shunt trip 220-250V DC / 208-277V AC, 2 auxiliary switches HQ, clamp connection.","salesMarkdown":"The Siemens 3VA1116-6ED36-0KC0 is a 3VA1 IEC frame 160 molded case circuit breaker with a 160 A fixed rating and a 70 kA breaking capacity at 415 V (class H). The breaker includes an integrated shunt trip (STL) rated for 220–250 V DC or 208–277 V AC, plus two HQ auxiliary switches. Connection is via clamp terminals. The 70 kA Icu at 415 V puts this breaker in the high-breaking-capacity class (H) for the 3VA1 frame. That SCCR matters when coordinating downstream with a transformer or a large motor branch circuit where fault current can exceed 50 kA — it avoids cascading failure upstream. The TM210 trip unit means the thermal element is sized for a 160 A continuous load; there is no adjustment range on Ir or Ii, so the breaker is a fixed-drop-in replacement for a 160 A branch. ## Deployment context The clamp connection accepts copper or aluminum conductors without lug kits, saving install time. The two HQ auxiliary switches provide independent status feedback for the open/closed position — one can feed a PLC input for remote indication, the other can lock out a contactor coil.","metaTitle":"Siemens 3VA1116-6ED36-0KC0 Circuit Breaker, 160A, 70kA @ 415","metaDescription":"Siemens 3VA1116-6ED36-0KC0 IEC frame 160 circuit breaker, 3-pole, 160A, 70kA breaking capacity at 415V. TM210 overload protection, shunt trip, 2 aux switches. Currently in producti","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=555495&mlfb=3VA1116-6ED36-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6ED36-0KC0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this circuit breaker?","answer":"It is a 3-pole IEC frame 160 breaker with a 160 A fixed rating, 70 kA breaking capacity at 415 V (class H), TM210 thermal-magnetic trip unit with Ir=160 A fixed and Ii=10 × In, a shunt trip for 220–250 V DC or 208–277 V AC, and two HQ auxiliary switches."},{"question":"Where can I buy 3VA1116-6ED36-0KC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6ED36-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6ED36-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}