{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6EF32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6EF32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6EF32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, 3VA1116-6EF32-0AA0, molded case circuit breaker (MCCB), 3-pole, 160 A (40 °C), TM240 thermal-magnetic release, 220 kA interrupting at 240 V.","salesMarkdown":"The Siemens 3VA1116-6EF32-0AA0 is a 3-pole SENTRON molded case circuit breaker rated for 160 A continuous at 40 °C, with a TM240 thermal-magnetic overcurrent release designed for line protection. At 55 °C it drops to 158 A, at 60 °C to 155 A, at 65 °C to 153 A, and at 70 °C to 150 A. That's a derating curve you can budget for. The TM240 release means the thermal element is calibrated for a 240 A frame; the magnetic pickup is fixed within that design. Dimensions are 70 mm deep, 76.2 mm wide, 130 mm high — a standard 3-pole MCCB footprint for DIN-rail or direct-mount panel integration. The 3VA series uses a common mounting pattern across the family, so swapping between current ratings within the same frame size doesn't require re-drilling the subplate.","metaTitle":"Siemens 3VA1116-6EF32-0AA0 SENTRON MCCB, 160 A, 3-Pole, TM24","metaDescription":"Siemens 3VA1116-6EF32-0AA0 SENTRON molded case circuit breaker, 160 A continuous at 40 °C, 220 kA at 240 V, 3-pole, TM240 release. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bc1e6d5b10d6b4e6521bae2330b897c4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=74772&mlfb=3VA1116-6EF32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA1116-6EF32-0AA0 at 240 V?","answer":"220 kA at 240 V. At 415 V it's 154 kA, at 440 V it's 75.6 kA, and at 690 V it's 17 kA."},{"question":"Where can I buy the 3VA1116-6EF32-0AA0?","answer":"This MCCB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of your quote request."},{"question":"What is the TM240 release on this MCCB?","answer":"TM240 is the designation of the thermal-magnetic overcurrent release. The '240' refers to the frame size; the breaker is rated 160 A continuous but the release mechanism is built on a 240 A platform. This is a line-protection design — not suitable for motor-starting duty without additional coordination."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6EF32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6EF32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}