{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6EF32-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6EF32-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6EF32-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF32-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-6EF32-0AG0, molded case circuit breaker, 3-pole, TM240 release, 160 A at 40 °C, 220 kA breaking capacity at 240 V, line protection design.","salesMarkdown":"At 40 °C it handles 160 A continuous, derating to 150 A at 70 °C. The interrupting ratings are the headline here: 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500/690 V — meaning it can clear high-fault currents on a transformer secondary or bus riser without upstream coordination headaches. The 160 A frame with TM240 release means the thermal pickup is adjustable up to 240 A, so you can dial it for the actual load, but the continuous ampacity at the terminals is 160 A at 40 °C. The 3-pole design covers three-phase loads; the built-in auxiliary switch plus trip alarm switch (HP type) gives remote status without an add-on module. Width is 76.2 mm (3 in), depth 70 mm, height 130 mm — fits standard MCCB panel cutouts and busbar spacing. The line protection designation means it's configured for cable/feeder protection out of the box, not motor or generator duty, so the trip curve is optimized for overload and short-circuit on distribution circuits. ## Panel integration Snap-on mounting for standard DIN rail or direct panel screw-mount via the rear slots.","metaTitle":"Siemens 3VA1116-6EF32-0AG0 SENTRON MCCB, 160 A, 220 kA at 24","metaDescription":"Siemens SENTRON 3VA1116-6EF32-0AG0 molded case circuit breaker, 3-pole, 160 A rated at 40 °C, TM240 release, 220 kA breaking at 240 V. Current lifecycle, available to order. Reques","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11166EF320AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HP","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=297589&mlfb=3VA1116-6EF32-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF32-0AG0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1116-6EF32-0AG0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate."},{"question":"What are the key ratings for 3VA1116-6EF32-0AG0?","answer":"160 A continuous at 40 °C, TM240 thermal-magnetic release, 3-pole, 220 kA interrupting at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500/690 V. Insulation voltage is 800 V. Dimensions: 76.2 mm wide, 70 mm deep, 130 mm tall."},{"question":"What compliance documentation is available for this MCCB?","answer":"This is a Siemens SENTRON series MCCB. Standard compliance documentation includes RoHS, REACH, and UL/IEC certifications as part of the SENTRON product family. Specific cert numbers are available on the product datasheet."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6EF32-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6EF32-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}