{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6EF32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6EF32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6EF32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-6EF32-0JH0, molded case circuit breaker, 3-pole, 160 A rated continuous current Iu, TM240 overcurrent release, breaking capacity 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, 17 kA at 690 V.","salesMarkdown":"## Line protection MCCB — 160 A, TM240, high breaking capacity The 3VA1116-6EF32-0JH0: Breaking capacity is 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. The overcurrent release is a TM240 — a thermal-magnetic type with a fixed rating of 160 A at 40 °C ambient, derating to 144 A at 70 °C. The breaker includes a voltage trigger and a trip indicator. Width is 76.2 mm, depth 70 mm, height 130 mm. Verify gland plate clearance for the 70 mm depth, especially in shallow enclosures. The manufacturer lists this part as current production.","metaTitle":"Siemens 3VA1116-6EF32-0JH0 SENTRON MCCB, 160 A, 3-Pole, 220","metaDescription":"Siemens SENTRON 3VA1116-6EF32-0JH0 molded case circuit breaker, 160 A rated current, 3-pole, TM240 release, breaking capacity 220 kA at 240 V. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"800 A","Adjustable response value current / lr min.":"112 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=11160&mlfb=3VA1116-6EF32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1116-6EF32-0JH0 at 415 V?","answer":"154 kA at 415 V."},{"question":"Where can I buy 3VA1116-6EF32-0JH0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6EF32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6EF32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}