{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6EF36-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6EF36-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6EF36-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF36-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-6EF36-0AB0, molded case circuit breaker, 3-pole, 160 A, TM240 thermal-magnetic release, line protection version, 220 kA at 240 V.","salesMarkdown":"At 440 V the breaking capacity drops to 75.6 kA, then to 17 kA at both 500 V and 690 V. For a 160 A frame this is a high-interrupting-capacity variant — not every MCCB in the 3VA family carries 220 kA at 240 V. At 55 °C it drops to 158 A, at 60 °C to 155 A, and at 70 °C to 150 A. If the enclosure runs hot (stacked breakers, poor airflow), the 150 A floor at 70 °C still leaves headroom for a 150 A feeder. The maximum power loss is 38 W, which factors into the enclosure thermal budget. Dimensions are 76.2 mm wide (3 in), 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that fits most Siemens SENTRON mounting plates and DIN-rail adapters.","metaTitle":"Siemens 3VA1116-6EF36-0AB0 SENTRON MCCB, 160 A, 3-Pole, 220","metaDescription":"Siemens SENTRON 3VA1116-6EF36-0AB0 molded case circuit breaker, 160 A, 3-pole, TM240 release, 220 kA at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","Auxiliary contact version":"2 auxiliary switches HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA11166EF360AA0","Courant permanent assigné Iu":"160 A","Design Of The Auxiliary Release":"without auxiliaryrelease","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg min.":"1","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"800 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b5460fdcdc91ad44ffa40ded580083b4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=279650&mlfb=3VA1116-6EF36-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF36-0AB0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA1116-6EF36-0AB0 include an undervoltage release?","answer":"No, this variant has no undervoltage release and no voltage trigger. It ships with a TM240 thermal-magnetic overcurrent release only."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6EF36-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6EF36-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}