{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6EF36-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6EF36-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6EF36-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF36-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-6EF36-0JA0, molded case circuit breaker, 3-pole, 160 A rated continuous current, TM240 overcurrent release, line protection, 220 kA at 240 V.","salesMarkdown":"## Siemens SENTRON 3VA1116-6EF36-0JA0 — 160 A MCCB with TM240 Release Its TM240 thermal-magnetic overcurrent release provides fixed trip curves for overload and short-circuit protection without the need for external trip units. The interrupting capacity reaches 220 kA at 240 V, 154 kA at 415 V, and 75.6 kA at 440 V — figures that govern its suitability for high-fault installations like transformer secondaries or large motor control centers. The 160 A rating holds flat from 40 °C through 50 °C, then derates to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. Plan your load margin accordingly. No interchangeable trip units, no field-adjustable long-time or short-time pickup. That simplifies ordering and reduces the chance of mis-configuration, but it also means the breaker is dedicated to its 160 A frame. If your load changes, you swap the whole MCCB, not just the trip. The shunt trip (STL) auxiliary release is built in — order code 3VA9688-0BL32 for the integrated auxiliary trip. No undervoltage release, no ground fault monitoring, no phase failure detection. If you need remote tripping via a PLC or E-stop circuit, the shunt trip covers that; if you need undervoltage protection, you add an external UVR module.","metaTitle":"Siemens 3VA1116-6EF36-0JA0 SENTRON MCCB, 160 A, 3-Pole, 220","metaDescription":"Siemens SENTRON 3VA1116-6EF36-0JA0 molded case circuit breaker, 160 A rated, 3-pole, line protection. SCCR 220 kA at 240 V. TM240 release, shunt trip. Current lifecycle stage. Quot","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"800 A","Adjustable response value current / lr min.":"112 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=237027&mlfb=3VA1116-6EF36-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF36-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA1116-6EF36-0JA0 drop into a panel specified around 3VA1110-5EE32-0JA0?","answer":"Yes, the 70 mm depth and 76.2 mm width are identical across the 3VA111x frame, so it fits the same busbar system and DIN-rail mounting without rewiring the panel layout."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6EF36-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6EF36-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}