{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6EF36-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6EF36-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6EF36-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF36-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-6EF36-0JH0, 3-pole molded case circuit breaker, 160 A rated continuous current (Iu), TM240 thermal-magnetic release, 220 kA interrupting at 240 V, shunt trip (STL), IP40 front, 70 x 76.2 x 130 mm.","salesMarkdown":"## SENTRON 3VA1116-6EF36-0JH0 — 160 A MCCB, line protection, shunt trip It is configured for line protection — no ground-fault monitoring, no phase-failure detection, no communication module. The interrupting ratings climb to 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V, which covers most industrial distribution panels and motor control center feeder positions. The breaker carries an IP40 rating on the front face, sufficient for general-purpose panel mounting where drip shields or higher ingress protection are not required. Above that, the breaker derates: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. The 3-pole footprint matches the standard 3VA111x frame width. The breaker mounts via screw-clamp terminals on the line and load sides — no DIN-rail clip. The shunt trip (STL) and auxiliary contact block are integrated into the breaker body, so the overall depth stays at 70 mm including the accessory stack. The IP40 front face is suitable for enclosed panel mounting; no additional gasketing needed for standard indoor environments.","metaTitle":"Siemens 3VA1116-6EF36-0JH0 SENTRON MCCB, 160 A, 220 kA at 24","metaDescription":"Siemens 3VA1116-6EF36-0JH0 SENTRON molded case circuit breaker, 160 A rated, 220 kA at 240 V, 3-pole, line protection, TM240 release, shunt trip, IP40 front. In current production,","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"800 A","Adjustable response value current / lr min.":"112 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=41308&mlfb=3VA1116-6EF36-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6EF36-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-6EF36-0JH0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting rating of 3VA1116-6EF36-0JH0 at 240 V?","answer":"220 kA at 240 V. The breaker also carries 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V."},{"question":"What auxiliary contacts does this MCCB include?","answer":"It comes with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration), and a factory-installed shunt trip (STL) release."},{"question":"Does 3VA1116-6EF36-0JH0 include ground fault or phase failure protection?","answer":"No. This variant is configured for line protection only — no ground fault monitoring, no phase failure detection, and no communication function."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6EF36-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6EF36-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}