{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6GD46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6GD46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6GD46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6GD46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-6GD46-0AA0, 4-pole molded case circuit breaker, 160 A frame, TM210 thermal-magnetic trip, 220 kA at 240 V, 70 mm depth.","salesMarkdown":"Its interrupting capacity reaches 220 kA at 240 V AC, dropping to 154 kA at 415 V and 75.6 kA at 440 V — figures that govern selectivity and SCCR coordination downstream. At 690 V it still clears 17 kA, so this frame handles industrial supply voltages without cascading upstream breakers. Full 160 A rating holds through 50 °C ambient; at 55 °C it derates to 158 A, at 60 °C to 155 A, and at 70 °C to 150 A. That means in a sealed enclosure with no forced cooling you still get 150 A of continuous capacity. The 70 mm depth and 101.6 mm width fit standard MCCB mounting footprints — check gland-plate clearance for the 4-pole lug arrangement. Maximum power loss is 38 W, which matters for thermal rise in a multi-breaker lineup. ## Compliance and approvals context Rated insulation voltage 800 V, IP40 on the front face. The TM210 overcurrent release provides thermal-magnetic protection for line distribution. Standard compliance documentation (CE, UL, IEC 60947-2) applies per the SENTRON series; verify specific certification marks for your jurisdiction at quote time.","metaTitle":"Siemens 3VA1116-6GD46-0AA0 SENTRON MCCB, 160 A, 4-Pole, 220","metaDescription":"Siemens SENTRON 3VA1116-6GD46-0AA0 molded case circuit breaker, 160 A, 4-pole, TM210 trip unit. 220 kA at 240 V, 154 kA at 415 V. Line protection. Active production. Available to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"160 A","Minimum":"160 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d812eda0f8bb3ee4db2d4f748ed7f941.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=101448&mlfb=3VA1116-6GD46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6GD46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1116-6GD46-0AA0 at different voltages?","answer":"220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. These values determine selectivity coordination with downstream breakers."},{"question":"What are the physical dimensions of this MCCB?","answer":"Depth 70 mm, width 101.6 mm, height 130 mm. The 4-pole frame fits standard MCCB mounting footprints with gland-plate clearance for the line and load lugs."},{"question":"Where can I buy 3VA1116-6GD46-0AA0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ with your target volume and delivery window; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6GD46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6GD46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}