{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-6GF46-0KF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-6GF46-0KF0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-6GF46-0KF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6GF46-0KF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1 series, molded case circuit breaker, 160 A frame, breaking capacity class H, 70 kA @ 415 V, 4-pole, line protection, TM240 thermal-magnetic release, shunt trip (STL), 1 auxiliary switch HQ + 1 trip alarm switch HQ, front terminal.","salesMarkdown":"## MCCB for line protection with integrated shunt trip The TM240 release provides LI protection — thermal overload (Ir adjustable 112–160 A) and magnetic short-circuit (Ii adjustable 5–10 × In) — sized for feeder or main distribution duty in commercial and industrial switchboards. The 4-pole design with 100% N-conductor protection means the neutral pole is fully rated and switched — required where harmonic currents or unbalanced loads demand a protected neutral path. The auxiliary contact pack — one HQ auxiliary switch plus one HQ trip alarm switch (order code 3VA9988-0AB12) — provides status feedback for remote indication and monitoring. ## Mounting and connection Front-terminal connection on the main current circuit accepts lug-type conductors, typical for panel-mounted MCCBs where busbar or cable access is from the front. The 15 000-cycle mechanical endurance is standard for a distribution-class MCCB in non-frequent switching service.","metaTitle":"Siemens 3VA1116-6GF46-0KF0 SENTRON MCCB, 160 A, 70 kA @ 415","metaDescription":"Siemens SENTRON 3VA1116-6GF46-0KF0 molded case circuit breaker, 160 A frame, 70 kA @ 415 V breaking capacity, TM240 release, shunt trip, 4-pole. Current production. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Trip indicator":"Yes","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Undervoltage Release With Leading Contact":"No","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Max. rated operational current of the frame size":"160 A","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=878019&mlfb=3VA1116-6GF46-0KF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-6GF46-0KF0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the 3VA1116-6GF46-0KF0?","answer":"160 A frame size, breaking capacity class H at 70 kA / 415 V AC, 4-pole with 100% N-conductor protection, TM240 thermal-magnetic release (Ir 112–160 A, Ii 5–10 × In), shunt trip (STL) for remote tripping, and one HQ auxiliary switch plus one HQ trip alarm switch."},{"question":"Where can I buy the 3VA1116-6GF46-0KF0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"As a SENTRON 3VA1 series device, it is designed to IEC 60947-2 and carries CE marking for the European market. RoHS and REACH declarations are standard from Siemens. For specific UL or marine classification documentation, verify the exact variant against the manufacturer's compliance matrix at time of order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-6GF46-0KF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-6GF46-0KF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}