{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1120-3ED46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1120-3ED46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1120-3ED46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1120-3ED46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1120-3ED46-0AA0, molded case circuit breaker, line protection, 4-pole, 20 A at 40 °C, TM210 release, breaking capacity 75.6 kA at 240 V, IP40 front, 70 mm deep.","salesMarkdown":"## Siemens 3VA1120-3ED46-0AA0 — MCCB for Line Protection Breaking capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V, with 11.9 kA available at 500 V and 690 V. The front face is IP40 rated, suitable for enclosed panel mounting. At 240 V the 75.6 kA breaking capacity gives substantial fault-current headroom for most North American 120/240 V split-phase or 240 V single-phase services. At 415 V (common in European 400 V systems) the 52.5 kA rating still covers high-fault utility connections. The 32 kA at 440 V and 11.9 kA at 500/690 V tell you this breaker is not sized for 690 V heavy industrial — at that voltage you need a higher-rated frame. For a 400 V panel with a prospective short-circuit current under 50 kA, this unit coordinates cleanly with upstream 63 A or 100 A SENTRON fuses or breakers. Depth 70 mm, width 101.6 mm (4 in), height 130 mm (5.12 in). The 101.6 mm width is a standard 4-pole MCCB footprint — it occupies the same DIN-rail or mounting-plate slot as other 4-pole SENTRON 3VA breakers of similar rating. No special adapter needed for standard 35 mm DIN rail. Power loss is 12 W maximum, which is moderate for a 20 A 4-pole breaker; ventilation in the enclosure should handle that without forced airflow.","metaTitle":"Siemens 3VA1120-3ED46-0AA0 SENTRON MCCB, 20A 4P 75.6kA 240V","metaDescription":"Siemens 3VA1120-3ED46-0AA0 SENTRON molded case circuit breaker, 20A at 40°C, 4-pole, breaking capacity 75.6kA at 240V. Active production, quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"20 A","at 45 °C":"20 A","at 50 °C":"20 A","at 55 °C":"20 A","at 60 °C":"19 A","at 65 °C":"19 A","at 70 °C":"19 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"without","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=446307&mlfb=3VA1120-3ED46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1120-3ED46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1120-3ED46-0AA0 and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA1120-3ED46-0AA0 at 240 V?","answer":"75.6 kA at 240 V, with lower ratings at higher voltages: 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V and 690 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1120-3ED46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1120-3ED46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}