{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1120-3GD42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1120-3GD42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1120-3GD42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1120-3GD42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1120-3GD42-0AA0, molded case circuit breaker, 4-pole, 20 A, TM210 thermal-magnetic release, line protection, 75.6 kA breaking capacity at 240 V AC.","salesMarkdown":"The 75.6 kA interrupting rating at 240 V AC gives it the headroom to clear high-fault currents without upstream coordination issues; at 415 V it still holds 52.5 kA, and at 690 V it drops to 11.9 kA, which is typical for this frame size. ## Ratings that matter for panel fit Dimensions are 130 mm height, 101.6 mm width, 70 mm depth — standard for the 3VA1 frame, so it mounts on a DIN rail or panel-mount plate without surprises. ## Coordination and selectivity notes The TM210 release is thermal-magnetic — fixed thermal pickup for overload, magnetic for short-circuit. If you need selectivity with a downstream 20 A MCB, the MCCB's magnetic trip threshold (typically 10x In for TM releases) should coordinate, but you'll want to verify with the selectivity tables in the 3VA manual.","metaTitle":"Siemens 3VA1120-3GD42-0AA0 SENTRON MCCB, 20 A, 4-Pole, 75.6","metaDescription":"Siemens 3VA1120-3GD42-0AA0 SENTRON molded case circuit breaker, 20 A rated, 4-pole, TM210 release, 75.6 kA at 240 V. Active production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"20 A","Minimum":"20 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"20 A","at 45 °C":"20 A","at 50 °C":"20 A","at 55 °C":"20 A","at 60 °C":"19 A","at 65 °C":"19 A","at 70 °C":"19 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=278568&mlfb=3VA1120-3GD42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1120-3GD42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1120-3GD42-0AA0 and how is it quoted?","answer":"We source and quote this part to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers on the public page, but a quote request gets you the real numbers."},{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"75.6 kA at 240 V AC, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. The interrupting rating drops with voltage, which is normal for this frame class."},{"question":"Does this MCCB have a trip indicator or communication capability?","answer":"No. This variant has no trip indicator, no undervoltage release, and no communication function. It is a basic thermal-magnetic line protection breaker."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1120-3GD42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1120-3GD42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}