{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1120-6EF36-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1120-6EF36-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA1120-6EF36-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1120-6EF36-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1120-6EF36-0AB0, molded case circuit breaker, 3-pole, 20 A rated, breaking capacity 220 kA at 240 V, TM240 thermal-magnetic release, line protection design.","salesMarkdown":"The Siemens 3VA1120-6EF36-0AB0 is a SENTRON molded case circuit breaker (MCCB) for line protection, rated 20 A continuous at 40 °C and carrying a 220 kA breaking capacity at 240 VAC. That interrupting rating drops to 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V or 690 V — so the voltage class of your distribution panel determines whether this breaker clears a fault without upstream coordination. The auxiliary switch bay carries two HP-style switches. The supplied basic switch order code is 3VA11206EF360AA0. ## Current derating and panel fit Rated 20 A from 40 °C through 55 °C; at 60 °C it holds 19 A, and at 70 °C it still holds 19 A (–). Maximum power loss is 12 W, low enough that adjacent devices see minimal heat rise. Width at 76.2 mm is a standard 3-module footprint on DIN rail; verify the busbar pitch matches your distribution block before committing the BOM.","metaTitle":"Siemens 3VA1120-6EF36-0AB0 SENTRON MCCB, 3-Pole, 20A, 220 kA","metaDescription":"Siemens 3VA1120-6EF36-0AB0 SENTRON molded case circuit breaker, 3-pole, 20A rated, 220 kA breaking capacity at 240 VAC. Active production, sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"20 A","at 45 °C":"20 A","at 50 °C":"20 A","at 55 °C":"20 A","at 60 °C":"19 A","at 65 °C":"19 A","at 70 °C":"19 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11206EF360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HP","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=238029&mlfb=3VA1120-6EF36-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1120-6EF36-0AB0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1120-6EF36-0AB0 at 240 V?","answer":"220 kA at 240 VAC. At 415 V it is 154 kA, at 440 V it is 121 kA, and at 500 V or 690 V it is 17 kA."},{"question":"Where can I buy 3VA1120-6EF36-0AB0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1120-6EF36-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1120-6EF36-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}