{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1125-3ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1125-3ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1125-3ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1125-3ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1125-3ED22-0AA0, molded case circuit breaker, 2-pole, 25 A at 40 °C, TM210 release, 75.6 kA breaking capacity at 240 V AC.","salesMarkdown":"## Siemens 3VA1125-3ED22-0AA0 — SENTRON MCCB for Line Protection Rated 25 A continuously at 40 °C ambient, with thermal derating to 23 A at 70 °C — the TM210 thermal-magnetic release handles overload and short-circuit protection in a single unit. Breaking capacity reaches 75.6 kA at 240 V AC and 52.5 kA at 415 V AC, sufficient for high-fault-current commercial and light industrial feeders. The 2-pole configuration with IP40 front protection suits panel-mount installations where the front face is exposed but the bus area remains enclosed. At 70 mm deep, 50.8 mm wide, and 130 mm tall, this MCCB occupies a standard 2-pole modular footprint — 50.8 mm (2 inches) per pole on the DIN rail, matching the SENTRON 3VA family spacing. Rated insulation voltage of 500 V and operating voltages up to 415 V AC or 250 V DC cover common panel bus voltages in North American and IEC markets. The 3VA1125-3ED22-0AA0 is listed as current production.","metaTitle":"Siemens 3VA1125-3ED22-0AA0 SENTRON MCCB, 25 A, 2-Pole, TM210","metaDescription":"Siemens 3VA1125-3ED22-0AA0 SENTRON molded case circuit breaker, 25 A at 40 °C, 2-pole, TM210 release, 75.6 kA at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 40 °C":"25 A","at 45 °C":"25 A","at 50 °C":"25 A","at 55 °C":"24 A","at 60 °C":"24 A","at 65 °C":"23 A","at 70 °C":"23 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"5.66 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2cfc857cf19c4400f197aef37f9ceb92.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=274236&mlfb=3VA1125-3ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1125-3ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What overcurrent release does this MCCB use?","answer":"The TM210 thermal-magnetic release provides both overload and short-circuit protection in a single, non-interchangeable unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1125-3ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1125-3ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}