{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1125-6EF32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1125-6EF32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1125-6EF32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1125-6EF32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1125-6EF32-0CH0, molded case circuit breaker, 3-pole, 25 A, TM240 overcurrent release, 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, 17 kA at 690 V.","salesMarkdown":"The 3VA1125-6EF32-0CH0: This 3-pole SENTRON MCCB carries a TM240 thermal-magnetic overcurrent release and is rated 25 A continuous at 40 °C through 50 °C, derating to 22.5 A at 70 °C. The interrupting ratings are what decide panel coordination: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V. At 690 V the 17 kA rating still covers most industrial motor-circuit faults. ## Auxiliary Contacts & Releases — Panel Wiring Note The UVR ensures the breaker trips on loss of control voltage — standard for safety circuits where a voltage-drop must open the load. The auxiliary contact wiring is accessible from the front terminal block; verify the free-wheel diode polarity on the UVR coil before energizing. The auxiliary trip module is order code 3VA9608-0BB24. ## Physical Fit — Panel Cutout & Mounting If your existing panel was cut for a 3VA1010-2ED32-0JA0 or similar 3VA frame, the width and depth are identical — the 3VA1125-6EF32-0CH0 drops into the same mounting slots without rewiring.","metaTitle":"Siemens 3VA1125-6EF32-0CH0 SENTRON MCCB, 25 A, 3-Pole, 220 k","metaDescription":"Siemens SENTRON 3VA1125-6EF32-0CH0 molded case circuit breaker, 25 A rated, 3-pole, 220 kA interrupting at 240 V. Current lifecycle. Quoted to order. RFQ for availability and prici","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"25 A","at 45 °C":"25 A","at 50 °C":"25 A","at 55 °C":"24 A","at 60 °C":"23.5 A","at 65 °C":"23 A","at 70 °C":"22.5 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"25 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"25 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"160 A","Adjustable response value current / lr min.":"18 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=200980&mlfb=3VA1125-6EF32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1125-6EF32-0CH0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1125-6EF32-0CH0 at different voltages?","answer":"At 240 V it is rated 220 kA, at 415 V it is 154 kA, at 440 V it is 121 kA, and at 690 V it is 17 kA."},{"question":"Will 3VA1125-6EF32-0CH0 drop into a panel specified around 3VA1010-2ED32-0JA0?","answer":"Yes, the 3VA1125-6EF32-0CH0 shares the same 76.2 mm width and 70 mm depth as the 3VA1010 frame, so it fits the same mounting slots and bus connections without rewiring."},{"question":"Where can I buy 3VA1125-6EF32-0CH0 and how is it quoted?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1125-6EF32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1125-6EF32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}