{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1125-6EF32-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1125-6EF32-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1125-6EF32-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1125-6EF32-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1125-6EF32-0KC0, 3-pole molded case circuit breaker, 25 A, 220 kA at 240 V, line protection, with shunt trip (STL) and 2 auxiliary switches HQ.","salesMarkdown":"The Siemens 3VA1125-6EF32-0KC0 is a SENTRON molded case circuit breaker (MCCB) rated 25 A continuous at 40–50 °C, with a 3-pole line-protection design. Its interrupting capacity climbs to 220 kA at 240 V, drops to 154 kA at 415 V, and holds at 121 kA at 440 V — then falls sharply to 17 kA at 500 V and 690 V. ## Integration and auxiliary content This MCCB ships with a factory-fitted shunt trip (STL) release and two HQ auxiliary switches — no field assembly needed for remote trip or status feedback. The 70 mm depth and 76.2 mm width fit standard Siemens 3VA panel-mounting footprints; the 130 mm height aligns with the 3VA1 frame. Maximum power loss is 8.5 W, which matters for enclosure thermal calculations in sealed panels.","metaTitle":"Siemens 3VA1125-6EF32-0KC0 SENTRON MCCB, 25 A, 220 kA at 240","metaDescription":"Siemens 3VA1125-6EF32-0KC0 SENTRON molded case circuit breaker, 25 A rated at 40-50 °C, 3-pole, 220 kA breaking capacity at 240 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"25 A","at 45 °C":"25 A","at 50 °C":"25 A","at 55 °C":"24 A","at 60 °C":"24 A","at 65 °C":"23 A","at 70 °C":"23 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"8.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11256EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=459113&mlfb=3VA1125-6EF32-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1125-6EF32-0KC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1125-6EF32-0KC0 at different voltages?","answer":"220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V — the high 240 V rating suits high-fault-current distribution panels."},{"question":"What auxiliary switches and releases come on this MCCB?","answer":"It includes a shunt trip (STL) release and two HQ auxiliary switches, factory-installed — no separate ordering or field fitting needed for remote trip and status."},{"question":"Where can I buy 3VA1125-6EF32-0KC0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"Will 3VA1125-6EF32-0KC0 drop into a panel specified for 5SQ2370-2YA05?","answer":"No direct drop-in — the 5SQ2370 series is a different form factor and accessory set. The 3VA1125-6EF32-0KC0 has its own mounting footprint (70 mm deep, 76.2 mm wide) and integrated shunt trip; verify panel cutout and wiring before substitution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1125-6EF32-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1125-6EF32-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}