{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-3ED12-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-3ED12-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-3ED12-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3ED12-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-3ED12-0AA0, molded case circuit breaker, 1-pole, 32 A (40 °C), TM210 thermal-magnetic release, 52.5 kA interrupting at 240 V AC, IP40 front.","salesMarkdown":"At 40 °C it carries 32 A continuously, derating to 30 A at 70 °C. Rated interrupting capacity is 52.5 kA at 240 V AC and 7.5 kA at 415 V AC. At 240 V that covers most North American commercial and light industrial service-entrance requirements; at 415 V the 7.5 kA figure is typical for European distribution boards where upstream transformers limit fault current. The 1-pole form factor fits a 25.4 mm (1 in) wide slot on the DIN rail — standard for single-phase branch circuits. Depth is 70 mm (2.76 in), which leaves clearance behind most standard panel doors.","metaTitle":"Siemens 3VA1132-3ED12-0AA0 SENTRON MCCB, 1-Pole, 32 A, TM210","metaDescription":"Siemens SENTRON 3VA1132-3ED12-0AA0 molded case circuit breaker, 1-pole, 32 A rated at 40 °C, TM210 release, 52.5 kA at 240 V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"25.4 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"1 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"1","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"3.53 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"125 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=346097&mlfb=3VA1132-3ED12-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3ED12-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-3ED12-0AA0 and how do I get a price?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is 3VA1132-3ED12-0AA0's listed depth (70 mm) on this component line?","answer":"Depth is 70 mm (2.76 in), width 25.4 mm (1 in), height 130 mm (5.12 in). The 1-pole footprint fits a standard DIN-rail slot."},{"question":"Will 3VA1132-3ED12-0AA0 drop into a panel that was specified around 3VA1110-5ED32-0AA0 without rewiring?","answer":"Both are 1-pole SENTRON 3VA MCCBs with the same physical footprint (25.4 mm wide, 70 mm deep, 130 mm high), so they share the same DIN-rail slot and bus-bar spacing. The 3VA1132-3ED12-0AA0 uses a TM210 release (32 A, fixed magnetic at 10× In), while the 3VA1110-5ED32-0AA0 uses a different release variant — verify the trip curve and interrupting rating match your coordination study before swapping."},{"question":"What compliance documentation does this brand provide for 3VA1132-3ED12-0AA0 (RoHS, REACH, UL, IEC)?","answer":"Siemens provides CE, UL, CSA, and IEC 60947-2 declarations for the SENTRON 3VA series. RoHS and REACH compliance statements are available through the Siemens Industry Online Support portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-3ED12-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-3ED12-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}