{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-3EE32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-3EE32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-3EE32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3EE32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1 series, Molded case circuit breaker, order code 3VA1132-3EE32-0AA0, 3-pole, 32 A, TM220 overcurrent release, interrupting rating 75.6 kA at 240 V.","salesMarkdown":"The interrupting ratings climb to 75.6 kA at 240 V, stepping down to 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V, per the datasheet. ## Thermal derating and operating envelope At 55 °C it drops to 31 A, at 65 °C to 30 A, and at 70 °C to 30 A. That is a 6.25% reduction at the top end, which is tighter than many MCCBs that start derating at 40 °C. The 3VA1132-3EE32-0AA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. That 76.2 mm (3 in) width is a standard 3-pole MCCB footprint — it fits existing DIN-rail or panel-mount cutouts sized for a 3-module-wide breaker.","metaTitle":"Siemens 3VA1132-3EE32-0AA0 SENTRON MCCB, 32 A, 3-Pole, TM220","metaDescription":"Siemens 3VA1132-3EE32-0AA0 SENTRON molded case circuit breaker, 32 A rated at 40 °C, 3-pole, TM220 release, 75.6 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=61863&mlfb=3VA1132-3EE32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3EE32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the interrupting ratings for 3VA1132-3EE32-0AA0 at different voltages?","answer":"At 240 V the interrupting rating is 75.6 kA, at 415 V it is 52.5 kA, at 440 V it is 32 kA, and at both 500 V and 690 V it is 11.9 kA."},{"question":"What does the TM220 release designation mean on this MCCB?","answer":"TM220 means a thermal-magnetic overcurrent release — the thermal element protects against sustained overloads, the magnetic element against short-circuits. There is no electronic trip unit, so no adjustable trip curves or communication."},{"question":"How do I get current pricing and availability for 3VA1132-3EE32-0AA0?","answer":"This part is sourced to order through independent distribution. Submit an RFQ; current pricing and availability are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-3EE32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-3EE32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}