{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-3EF32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-3EF32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-3EF32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3EF32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-3EF32-0CH0, molded case circuit breaker, 3-pole, 32 A rated current at 40 °C, line protection design, 75.6 kA breaking capacity at 240 V AC.","salesMarkdown":"## Siemens 3VA1132-3EF32-0CH0 — SENTRON MCCB for Line Protection The 3-pole construction handles three-phase circuits up to 800 V rated insulation voltage. Breaking capacity is 75.6 kA at 240 V AC, 52.5 kA at 415 V, and 32 kA at 440 V — figures that govern selectivity coordination with downstream branch breakers. The trip indicator confirms the breaker has opened on fault, useful during troubleshooting without removing the cover. Power loss is 13.1 W maximum — factor this into enclosure thermal calculations for derating.","metaTitle":"Siemens 3VA1132-3EF32-0CH0 SENTRON MCCB, 32A, 3-Pole, 75.6kA","metaDescription":"Siemens 3VA1132-3EF32-0CH0 SENTRON molded case circuit breaker, 32A rated at 40°C, 3-pole, 75.6kA interrupting at 240V. Active production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11323EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=269001&mlfb=3VA1132-3EF32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3EF32-0CH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1132-3EF32-0CH0 at 415 V?","answer":"The interrupting rating is 52.5 kA at 415 V AC, which is the common European distribution voltage for selectivity studies."},{"question":"Where can I buy 3VA1132-3EF32-0CH0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What auxiliary switches come with this MCCB?","answer":"The breaker ships with two auxiliary switches and one trip alarm switch (HQ configuration), plus an integrated undervoltage release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-3EF32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-3EF32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}