{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-3EF36-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-3EF36-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-3EF36-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3EF36-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-3EF36-0CC0, 3-pole molded case circuit breaker, 32 A rated continuous current, 75.6 kA breaking capacity at 240 V, TM240 thermal-magnetic release, IP40 front protection.","salesMarkdown":"It carries a continuous current Iu of 32 A at 40 °C through 50 °C, derating to 30.72 A at 55 °C and 28.8 A at 70 °C — a thermal curve that matters for panel fill factor and ambient placement. The TM240 thermal-magnetic release handles overload and short-circuit response without an electronic trip unit, keeping the design simple for distribution panels that don't need adjustable curves. Breaking capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V — these are the fault-clearing numbers that govern SCCR coordination downstream. For DC network applications, the manufacturer directs to the 3VA device manual for switching power values; the part itself is not pre-rated for DC in the basic listing. Depth is 70 mm, height 130 mm. No communication module, no voltage trigger, no phase failure detection — this is a plain line-protection breaker, not a metering or communicating device.","metaTitle":"Siemens 3VA1132-3EF36-0CC0 MCCB, 32 A, 75.6 kA at 240 V","metaDescription":"Siemens SENTRON 3VA1132-3EF36-0CC0 molded case circuit breaker, 32 A, 75.6 kA breaking at 240 V. Active production. Sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"10.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"160 A","Adjustable response value current / lr min.":"22 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=268474&mlfb=3VA1132-3EF36-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3EF36-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-3EF36-0CC0 and get a price?","answer":"The part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — stock levels and lead times are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA1132-3EF36-0CC0 at different voltages?","answer":"Breaking capacity is 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V."},{"question":"Does 3VA1132-3EF36-0CC0 include an undervoltage release?","answer":"Yes, it is equipped with an undervoltage release (UVR) as the auxiliary release design."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-3EF36-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-3EF36-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}