{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-3EF36-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-3EF36-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-3EF36-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3EF36-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-3EF36-0JC0, molded case circuit breaker, 3-pole, 32 A rated continuous current, TM240 overcurrent release, 75.6 kA at 240 V, 70 mm depth.","salesMarkdown":"## 32 A MCCB with TM240 release — line protection for 3-pole panels The Siemens 3VA1132-3EF36-0JC0 is a SENTRON molded case circuit breaker (MCCB) rated for 32 A continuous current at 40 °C, with a 3-pole configuration and a TM240 thermal-magnetic overcurrent release. The interrupting ratings climb to 75.6 kA at 240 V and still hold 10.5 kA at 690 V, so it clears high-fault scenarios across common low-voltage distribution voltages. Front face carries IP40 protection; the housing dimensions are 76.2 mm wide, 130 mm tall, 70 mm deep — standard DIN-rail or screw-mount footprint for a 3-pole MCCB in a panel enclosure. ## Derating curve and thermal limits Above that, it steps down: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. The depth of 70 mm and width of 76.2 mm fit standard 3-pole MCCB mounting footprints — check gland-plate clearance if the panel has shallow back-panel wiring troughs. ## Auxiliary and trip options on this variant The auxiliary release design is identified as 3VA9688-0BL32. Mechanical endurance is listed at 15,000 operations.","metaTitle":"Siemens 3VA1132-3EF36-0JC0 SENTRON MCCB, 32 A, 3-Pole, 75.6","metaDescription":"Siemens 3VA1132-3EF36-0JC0 SENTRON molded case circuit breaker, 32 A rated continuous current, 3-pole, 75.6 kA at 240 V. Current production lifecycle. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1132-3EF36-0JC0","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"10.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","description":"circuit breaker 3VA1 IEC frame 160 breaking capacity class N Icu=25kA @ 415V 3-pole, line protection TM240, ATAM, In=32A overload protection Ir=22A...32A short-circuit protection Ii=5...10 x In clamp connection shunt trip (STL) 110-127V DC, AC 50/60Hz 2 auxiliary switches HQ","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"160 A","Adjustable response value current / lr min.":"22 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=10397&mlfb=3VA1132-3EF36-0JC0"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for 3VA1132-3EF36-0JC0?","answer":"As a Siemens SENTRON MCCB, this part carries the manufacturer's standard compliance documentation including RoHS, REACH, and relevant IEC/UL certifications for molded case circuit breakers. Specific certificate numbers should be confirmed from the nameplate or the manufacturer's product documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-3EF36-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-3EF36-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}