{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-3GF46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-3GF46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-3GF46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3GF46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-3GF46-0AA0, molded case circuit breaker, 32 A, 4-pole, TM240 thermal-magnetic release, line protection design, IP40 front.","salesMarkdown":"Breaking capacity is 75.6 kA at 240 V and 11.9 kA at 690 V. ## Breaking capacity and derating The 32 A rating holds flat from 40 °C through 50 °C, then derates to 31 A at 55–60 °C and 30 A at 65–70 °C. That means in a warm panel — say 55 °C internal ambient — you lose 1 A of headroom. The 75.6 kA at 240 V is the highest interrupt rating; at 690 V it drops to 11.9 kA, so verify the available fault current at your line voltage before specifying. ## Panel fit Dimensions are 70 mm deep, 101.6 mm wide, 130 mm high — a 4-pole MCCB that occupies roughly 4 inches of DIN-rail width.","metaTitle":"Siemens 3VA1132-3GF46-0AA0 SENTRON MCCB, 32 A, 4-Pole, TM240","metaDescription":"Siemens 3VA1132-3GF46-0AA0 SENTRON molded case circuit breaker, 32 A, 4-pole, TM240 release, breaking capacity 75.6 kA at 240 V. Active production, available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"32 A","Minimum":"32 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=526821&mlfb=3VA1132-3GF46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-3GF46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA1132-3GF46-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0?","answer":"Both are 4-pole SENTRON MCCBs, but the 3VA1110-5ED32-0AA0 is a different frame size and release variant. Verify the mounting footprint and busbar spacing — the 3VA1132-3GF46-0AA0 has a 101.6 mm width and 70 mm depth; compare against your existing panel cutout and DIN-rail layout before assuming direct drop-in."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-3GF46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-3GF46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}