{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-4EF36-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-4EF36-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-4EF36-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-4EF36-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1 molded case circuit breaker, 3VA1132-4EF36-0JC0, 3-pole, 32 A, line protection, breaking capacity 121 kA at 240 V AC, 75.6 kA at 415 V, with shunt trip (STL) and 2 auxiliary switches HQ, 70 mm depth.","salesMarkdown":"Its 3-pole construction and 32 A rating (continuous at 40 °C through 50 °C, derating to 30 A at 70 °C) make it a fit for feeder or branch circuits in commercial and industrial switchboards. ## Breaking capacity — the real-world fault stop This MCCB carries a breaking capacity of 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. Rated 32 A continuous from 40 °C to 50 °C, it derates to 31 A at 55–60 °C and 30 A at 65–70 °C. In a closed panel with multiple breakers ganged, that derating curve governs the real ampacity — don't load it to 32 A if ambient inside the enclosure hits 55 °C. Dimensions are 130 mm tall, 76.2 mm wide, and 70 mm deep, fitting standard 3-pole MCCB footprints on DIN rail or panel-mount backplates. ## Auxiliaries and release options","metaTitle":"Siemens 3VA1132-4EF36-0JC0 SENTRON MCCB, 3-Pole, 32 A, 121 k","metaDescription":"Siemens 3VA1132-4EF36-0JC0 SENTRON molded case circuit breaker, 3-pole, 32 A rated at 40-70 °C, breaking capacity 121 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11324EF360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=421425&mlfb=3VA1132-4EF36-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-4EF36-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-4EF36-0JC0 and how do I get a price?","answer":"This MCCB is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm availability and current pricing."},{"question":"What is the breaking capacity of 3VA1132-4EF36-0JC0 at different voltages?","answer":"121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V."},{"question":"Does 3VA1132-4EF36-0JC0 include a shunt trip or auxiliary switches?","answer":"Yes, it comes with a shunt trip (STL) for remote opening and two HQ auxiliary switches for status signaling."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-4EF36-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-4EF36-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}