{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-4GD46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-4GD46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-4GD46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-4GD46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-4GD46-0AA0, molded case circuit breaker, 4-pole, 32 A, TM210 release, breaking capacity 121 kA at 240 V.","salesMarkdown":"## SENTRON 3VA1132-4GD46-0AA0 — 32 A MCCB with TM210 Release Breaking capacity reaches 121 kA at 240 V AC, dropping to 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V — figures that govern selectivity coordination with downstream breakers. At 415 V, common in European industrial panels, the 75.6 kA SCCR handles most transformer-fed fault levels without cascading upstream. Above that, current capacity tapers to 30 A at 70 °C — relevant for tightly packed enclosures where internal temperature rise is a concern. No successor or PCN/EOL notice has been announced for this order code. The SENTRON 3VA series is Siemens' current MCCB platform. The breaker occupies 101.6 mm width, 130 mm height, and 70 mm depth — a 4-pole footprint that fits standard Siemens 3VA panel mounting. Maximum power loss is 10.6 W, which contributes to enclosure thermal calculations. The TM210 release is factory-set and non-adjustable for thermal pickup, simplifying specification but requiring correct sizing at the design stage.","metaTitle":"Siemens 3VA1132-4GD46-0AA0 SENTRON MCCB, 32 A, 4-Pole, 121 k","metaDescription":"Siemens SENTRON 3VA1132-4GD46-0AA0 molded case circuit breaker, 32 A rated, 4-pole, TM210 release. Breaking capacity 121 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"32 A","Minimum":"32 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=269894&mlfb=3VA1132-4GD46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-4GD46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Does the 3VA1132-4GD46-0AA0 include undervoltage release or ground-fault monitoring?","answer":"No. This variant has no undervoltage release and no ground-fault monitoring — it is a straight thermal-magnetic line-protection breaker."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-4GD46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-4GD46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}