{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-4GF42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-4GF42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-4GF42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-4GF42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class S, Icu=36kA @ 415V, 4-pole, line protection TM240, ATAM, In=32A, overload protection Ir=22A...32A, short-circuit protection Ii=5...10 x In, N conductor protection 100%, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1132-4GF42-0AA0-ZD00 is a 4-pole IEC frame 160 circuit breaker rated for 32 A continuous current, with a breaking capacity of 36 kA at 415 V (class S). The TM240 thermal-magnetic trip unit provides overload protection adjustable from 22 A to 32 A, and short-circuit protection set at 5 to 10 times In. The 100% N-conductor protection means the neutral pole is fully rated and switched — essential for 4-wire systems where unbalanced loads or harmonics could overload a reduced-neutral breaker. This variant includes a nut keeper kit for DC Power OEM assembly in China.","metaTitle":"Siemens 3VA1132-4GF42-0AA0-ZD00 Circuit Breaker, 36kA @ 415V","metaDescription":"Siemens 3VA1132-4GF42-0AA0-ZD00 IEC frame 160 circuit breaker, 36kA breaking capacity at 415V, 4-pole, TM240 overload protection, Ir=22-32A. Lifecycle stage: current. Available to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667704&mlfb=3VA1132-4GF42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-4GF42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this circuit breaker?","answer":"The breaking capacity is 36 kA at 415 V (IEC frame 160, class S)."},{"question":"What are the overload and short-circuit protection settings?","answer":"Overload protection (Ir) is adjustable from 22 A to 32 A; short-circuit protection (Ii) is set at 5 to 10 times In (32 A)."},{"question":"Where can I buy 3VA1132-4GF42-0AA0-ZD00?","answer":"This part is available to order against an RFQ. Submit a request for current pricing and delivery lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-4GF42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-4GF42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}