{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-5ED32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-5ED32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-5ED32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5ED32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 3-pole, line protection TM210, FTFM, In=32A, Ir=32A fixed, Ii=10 x In, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1132-5ED32-0AA0-ZD00 is a 3-pole IEC frame 160 molded case circuit breaker with a 55 kA interrupting capacity at 415 V (breaking capacity class M). The unit includes a nut keeper kit and is designated for DC Power OEM production in China. The fixed Ii = 10 × In (320 A) is the magnetic instantaneous trip threshold — it clears bolted faults fast but may not coordinate with downstream branch breakers on moderate overcurrents. ## Panel integration At 32 A, no forced cooling is required, but maintain the manufacturer's recommended spacing between adjacent breakers for thermal derating — typically 10 mm on each side for full rated current. The nut keeper kit is a mechanical aid for captive screw retention during assembly, common in OEM production lines.","metaTitle":"Siemens 3VA1132-5ED32-0AA0-ZD00 Circuit Breaker, 55kA @ 415V","metaDescription":"Siemens 3VA1132-5ED32-0AA0-ZD00 IEC frame 160, 3-pole, 32A, Icu=55kA @ 415V. Lifecycle current. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667705&mlfb=3VA1132-5ED32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5ED32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of this breaker?","answer":"The 3VA1132-5ED32-0AA0-ZD00 has a rated ultimate short-circuit breaking capacity (Icu) of 55 kA at 415 V AC, placing it in breaking capacity class M."},{"question":"What are the fixed trip settings on this breaker?","answer":"Overload protection (Ir) is fixed at 32 A. Short-circuit protection (Ii) is fixed at 10 × In, which is 320 A."},{"question":"Where can I buy 3VA1132-5ED32-0AA0-ZD00?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-5ED32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-5ED32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}