{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-5ED36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-5ED36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-5ED36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5ED36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1 series, 3-pole molded case circuit breaker, 32 A rated current, TM210 thermal-magnetic release, 187 kA breaking capacity at 240 V AC.","salesMarkdown":"It carries three poles and a TM210 thermal-magnetic overcurrent release — the '210' designates a fixed thermal trip at 32 A and a magnetic short-circuit pickup at 10× In, per Siemens' TM release numbering. The breaker is rated for an insulation voltage of 800 V and delivers a maximum breaking capacity of 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. That spread tells you the interrupting capability drops sharply above 440 V — at 690 V it's still 17 kA, which covers most industrial motor branch circuits but not high-fault utility feeds. ## Thermal derating — what the 32 A rating actually means That's a shallow derating curve — only 2 A lost over a 30 °C rise — which is typical of the SENTRON 3VA1's thermal design. The breaker dissipates 10.6 W maximum at rated load, so ventilation in a sealed enclosure matters more for the surrounding components than for the breaker itself. The 3VA1132-5ED36-0AA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard 3-pole MCCB footprint that fits SENTRON mounting plates and most DIN-rail adapters. If you need those functions, you're looking at a different suffix in the 3VA1 family.","metaTitle":"Siemens 3VA1132-5ED36-0AA0 SENTRON MCCB, 3P, 32A, 187kA at 2","metaDescription":"Siemens SENTRON 3VA1132-5ED36-0AA0 molded case circuit breaker, 3-pole, 32A, TM210 release, 187kA breaking capacity at 240V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=99499&mlfb=3VA1132-5ED36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5ED36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-5ED36-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of 3VA1132-5ED36-0AA0 at different voltages?","answer":"At 240 V AC it interrupts 187 kA, at 415 V it's 121 kA, at 440 V it's 75.6 kA, and at both 500 V and 690 V it's 17 kA."},{"question":"What trip unit does 3VA1132-5ED36-0AA0 use?","answer":"It uses a TM210 thermal-magnetic overcurrent release — fixed thermal trip at 32 A, magnetic short-circuit pickup at 10× In."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-5ED36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-5ED36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}