{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-5EE42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-5EE42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-5EE42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5EE42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-5EE42-0AA0, 4-pole molded case circuit breaker, line protection, 32 A rated current, TM220 release, 187 kA at 240 V.","salesMarkdown":"It delivers 187 kA breaking capacity at 240 V, 121 kA at 415 V, and 75.6 kA at 440 V — these numbers tell you it can safely interrupt very high fault currents without upstream coordination issues. The adjustable li max of 320 A gives you a short-circuit pickup range to tune for the load. The 4-pole design covers three-phase plus neutral, with no integrated N-conductor protection (separate N protection is external). An optional motor drive (product extension) is available for remote switching. No communication function is built in, so any remote monitoring requires an external module or I/O.","metaTitle":"Siemens SENTRON 3VA1132-5EE42-0AA0 MCCB, 32 A, 187 kA at 240","metaDescription":"Siemens SENTRON 3VA1132-5EE42-0AA0 4-pole MCCB, 32 A rated, 187 kA at 240 V. Line protection, TM220 release. Current production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Number Of Poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"32 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"Without","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"600 V","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=141252&mlfb=3VA1132-5EE42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5EE42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA1132-5EE42-0AA0 and how is it quoted for volume purchases?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is 3VA1132-5EE42-0AA0's listed depth?","answer":"The depth is 70 mm (2.76 in), with a width of 101.6 mm (4 in) and height of 130 mm (5.12 in)."},{"question":"What compliance documentation does this brand provide for 3VA1132-5EE42-0AA0?","answer":"As a Siemens SENTRON MCCB, it carries the usual IEC/UL certifications (the reference code follows IEC 81346-2). Specific RoHS, REACH, and UL documentation is available from Siemens upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-5EE42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-5EE42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}