{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1132-5EF32-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1132-5EF32-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA1132-5EF32-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5EF32-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1132-5EF32-0AG0, molded case circuit breaker, 3-pole, 32 A, TM240 thermal-magnetic release, interrupting rating 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 17 kA at 500/690 V.","salesMarkdown":"It carries a 32 A continuous rating at 40 °C through 50 °C, derating to 30 A at 70 °C — that thermal curve matters if your panel runs hot. Three poles, 800 V rated insulation voltage, and interrupting ratings that step down from 187 kA at 240 V to 17 kA at 500/690 V. Dimensions: 130 mm high, 76.2 mm wide, 70 mm deep — that's a 3-inch wide footprint, standard for a 3-pole MCCB in this class. The auxiliary switch configuration is 1 auxiliary switch + 1 trip alarm switch HP, so you get a separate alarm contact for remote fault indication without adding an external module.","metaTitle":"Siemens 3VA1132-5EF32-0AG0 SENTRON MCCB, 32 A, 3-Pole, 187 k","metaDescription":"Siemens SENTRON 3VA1132-5EF32-0AG0 molded case circuit breaker, 32 A, 3-pole, interrupting rating 187 kA at 240 V. TM240 release. Current production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11325EF320AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HP","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3de18f10dd52266f770fd73388f1ee5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=85548&mlfb=3VA1132-5EF32-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1132-5EF32-0AG0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1132-5EF32-0AG0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3VA1132-5EF32-0AG0's interrupting rating at 240 V?","answer":"187 kA at 240 V, stepping down to 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500 V and 690 V."},{"question":"What overcurrent release does this MCCB use?","answer":"It uses a TM240 thermal-magnetic release — fixed thermal and magnetic settings, no electronic trip unit, no communication function."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1132-5EF32-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1132-5EF32-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}